EasyManua.ls Logo

Carrier 100 Series - General; Sequence of Operation

Carrier 100 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table
8—Horizontal
Vent
Termination
Clearances
LOCATION
CLEARANCE
(FT)
U.S.A.
Canada
Above
anticipated
snow
depth
1
14
From
mechanical
fresh
air
intake
1
6
For
furnaces
with
an
input
capacity
less
than
100,000
Btuh
from
any
nonmechanical
air
supply
(such
as
a
door
or
win¬
dow)
or
combustion-air
opening
4
below
4
horizontally
1
above
1
For
furnaces
with
an
input
capacity
greater
than
100,000
Btuh
from
any
nonmechanical
air
supply
(such
as
a
door
or
win¬
dow)
or
combustion-air
opening
3
From
service
regulator
vent,
electric
and
gas
meters
and
re¬
lief
equipment
4*
6t
Above
grade
when
adjacent
to
public
walkway
7
7
*HorizontaI
distance.
t36
in.
to
electric
meter.
$18
in.
above
roof
surface
in
Canada.
Horizontal
Vent
Termination
NOTE:
Do
not
locate
the
vent
termination
close
to
shrubbery.
Flue
gas
may
stunt
growth
or
kill
shrubs.
Combustion
products
may
affect
unprotected
building
material
surfaces.
Sealing
or
shielding
of
exposed
surfaces
with
a
corrosion
resistant
material
may
be
required
in
these
cases.
NOTE:
In
U.S.A.,
vent
must
terminate
3
ft
above
any
mechanical
fresh
air
intake
within
10
ft.
After
vent
system
is
installed,
inspect
all
joints
and
supports.
If
all
joints
are
secure,
fully
seated,
and
well
supported
by
straps,
furnace
may
be
started,
adjusted
per
furnace
Installation
Instruc¬
tions,
and
placed
into
operation.
See
vent
pipe
manufacture’s
Installation
Instructions:
cure
time
may
be
required
before
oper¬
ating
furnace.
Step
8—START-UP,
ADJUSTMENT,
AND
SAFETY
CHECK
GENERAL
The
furnace
must
have
a
115-v
power
supply
properly
connected
and
grounded.
Correct
polarity
must
be
maintained
to
enable
operation.
The
gas
service
pressure
must
not
exceed
0.5
PSIG
(14-m.
wc),
but
be
no
less
than
0.16
PSIG
(4.5-in.
wc).
Thermostat
wire
connections
at
R
and
WAVl
are
the
minimum
required
for
gas
heating
operation.
W2
must
be
connected
for
2-stage
heating
thermostats.
COM,
Y/Y2,
and
G
are
required
for
cooling,
heat
pumps,
and
some
clock
thermostats.
'Diese
must
be
made
at
the
24-v
terminal
block
on
the
control.
(See
Fig.
10.)
This
furnace
can
be
installed
with
either
a
single-stage
heating
or
a
2-stage
heating
thermostat.
For
single-stage
thermostats,
connect
thermostat
R
to
WAVl
at
the
furnace
control
terminal
block.
(See
Fig.
8.)
For
single-stage
thermostats,
the
control
will
determine,
based
on
length
of
previous
heating
cycles,
when
to
operate
in
low
and
high
gas
heat
for
optimum
comfort.
Setup
switch-2
(SW-2)
must
be
in
the
factory-shipped
OFF
position.
See
Fig.
11
and
Tables
9
and
10
for
setup
switch
information.
Table
9—Blower
Off
Delay
Setup
Switch
Position
DESIRED
HEATING
MODE
BLOWER
OFF
DELAY
(SEC)
SETUP
SWITCH
SW-3
SW-4
90
OFF
OFF
135
ON
OFF
180
OFF
ON
225
ON
ON
Table
10—Setup
Switch
(SW)
Description
SETUP
SWITCH
NO.
NORMAL
POSITION
DESCRIPTION
OF
USE
SW-1
High
Gas
Heat
OFF
Turn
switch
ON
to
obtain
high
gas
heat
operation
on
any
call
for
heat
regardless
of
whether
*R-W/W1,
or
R-W/W1,
-W2
is
closed.
SW-1
over¬
rides
SW-2.
SW-2
Low
Gas
Heat
OFF
Turn
switch
OFF
for
installations
with
single-stage
thermostats;
con¬
trol
selects
low
gas
heat
or
high
gas
heat
operation
based
on
previous
cycles.
Turn
switch
ON
for
installa¬
tions
with
2-stage
thermostats
to
permit
only
low
gas
heat
operation
in
response
to
closing
*R-W/W1.
High
gas
heat
is
supplied
only
when
R
to
W/W1
and
W2
is
closed.
SW-3,
and
SW4
ON,
OFF
Switches
control
gas
heating
mode
blower
off
delay.
See
Table
9.
K
a
2-stage
heating
thermostat
is
to
be
used,
move
SW2
to
the
ON
position
at
the
end
of
the
furnace
installation.
This
will
override
the
built-in
control
process
for
selecting
high
and
low
fire
and
allow
the
2-stage
thermostat
to
select
heating
modes.
The
W2
from
the
thermostat
must
be
connected
to
W2
on
the
control
terminal
block.
(See
Fig.
9.)
A
CAUTION
This
furnace
is
equipped
with
a
manual
reset
limit
switch
in
the
gas
control
area.
The
switch
will
open
and
shut
off
power
to
the
gas
valve
if
a
flame
rollout
or
overheating
condition
occurs
in
the
gas
control
area.
DO
NOT
bypass
the
switch.
Correct
inadequate
combustion-air
supply,
component
fail¬
ure,
or
restricted
flue
gas
passageway
and
reset
the
switch.
Before
operating
the
furnace,
check
each
manual
reset
switch
for
continuity.
If
necessary,
press
and
release
the
button
to
reset
the
switch.
SEQUENCE
OF
OPERATION
Using
the
schematic
diagram
in
Fig.
12,
follow
the
sequence
of
operation
through
the
different
modes.
Read
and
follow
the
diagram
very
carefully.
NOTE:
If
a
power
interruption
occurs
during
a
call
for
heat
(W/Wl
or
WAVl
and
W2)
and
if
the
thermostat
is
still
calling
for
gas
heating,
the
control
will
start
a
90-sec
blower-only
ON
period
2
sec
after
power
is
restored.
The
LED
red
light
will
flash
code
12
during
the
90-sec
period,
after
which
the
LED
will
be
ON
continuous,
as
long
as
no
faults
are
detected.
After
the
90-sec
10

Related product manuals