EasyManua.ls Logo

Carrier 100 Series - Temperature Rise; Thermostat Heat Anticipator; Check Safety Controls

Carrier 100 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTE:
If
orifice
hole
appears
damaged
or
it
is
suspected
to
have
been
redrilled,
check
the
orifice
size
with
a
numbered
drill
bit
of
the
correct
size.
Never
use
a
redrilled
orifice.
A
burr-free
and
squarely
aligned
orifice
hole
is
essential
for
proper
flame
charac¬
teristics.
(7.)
Remove
jumper
on
R-WAV1-W2
after
high-fire
ad¬
justments.
(8.)
Replace
gas
control
regulator
adjustment
caps.
(9.)
Remove
regulator
adjustment
seal
cap.
(See
Fig.
13.)
(10.)
Turn
adjusting
screw
counterclockwise
to
decrease
input.
Turn
screw
clockwise
to
increase
input.
DO
NOT
set
manifold
pressure
less
than
3.2
or
more
than
3.8-in.
maximum
wc
for
natural
gas.
Make
any
major
adjustments
by
changing
main
burner
orifices.
(11.)
When
correct
input
is
obtained,
replace
regulator
seal
cap.
Main
burner
flame
should
be
clear
blue,
almost
transparent.
(See
Fig.
14.)
2.
Set
temperature
rise.
Place
SW2
in
ON
position;
jumper
R
to
W/Wl
and
W2
to
check
high
gas
heat
temperature
rise.
To
check
low
gas
heat
temperature
rise,
remove
jumper
to
W2.
Determine
air
tem¬
perature
rise
for
both
high-
and
low-fire.
Do
not
exceed
the
temperature
rise
ranges
specified
on
the
unit
rating
plate
for
high
and
low
fire.
a.
P
lace
duct
thermometers
in
return
and
supply
ducts
as
near
furnace
as
possible.
Be
sure
thermometers
do
not
see
heat
exchangers
so
that
radiant
heat
will
not
affect
thermometer
readings.
This
is
particularly
important
with
straight
run
ducts.
BURNER
FUME
A
WARNING
Disconnect
the
electrical
power
before
changing
the
speed
tap.
A
failure
to
follow
this
warning
can
cause
personal
injury.
d.
To
change
motor
speed
taps,
remove
the
motor
tap
lead
and
relocate
it
on
the
desired
terminal
on
the
plug-in
terminal
block/speed
selector
located
on
the
blower
housing.
(See
Table
13.)
TAP
A93376
Fig.
13—Redundant
Automatic
Gas
Control
Valve
b.
When
thermometer
readings
stabilize,
subtract
return-air
temperature
from
supply-air
temperature
to
determine
tem¬
perature
rise.
NOTE:
If
the
temperature
rise
is
outside
this
range,
first
check:
(1.)
Gas
input
for
low
and
high
fire
operation.
(2.)
Derate
for
altitude
if
applicable.
(3.)
Return
and
supply
ducts
for
excessive
restrictions
causing
static
pressures
greater
than
0.50-in.
wc.
c.
Adjust
air
temperature
rise
by
adjusting
blower
speed.
Increase
blower
speed
to
reduce
temperature
rise.
Decrease
blower
speed
to
increase
temperature
rise.
For
high
fire,
speed
tap
selection
can
be
2
or
3
(factory
settings).
For
low
fire,
speed
tap
selection
can
be
4,
(factory
setting)
or
3
if
high
fire
speed
selection
is
2.
Table
13—Speed
Selector
SPEED
TAP
NO.*
Common
C
High
1
Med-High
2
Med-Low
3
Low
4
*
White
wire
from
control
box
to
common;
black
wire
from
control
box
to
high
cooling
speed
selection;
blue
wire
from
control
to
high
heating
speed
selection;
and
red
wire
from
control
to
low
heating/low
cooling/continuous
fan
speed
selection.
A
CAUTION
Recheck
the
temperature
rise.
It
must
be
within
the
limits
specified
on
the
unit
rating
plate.
Recommended
operation
is
at
mid
point
of
rise
or
above.
3.
Set
thermostat
heat
anticipator.
The
thermostat
heat
anticipation
must
be
set
to
match
the
amp
draw
of
the
electrical
components
in
the
R-W/Wl
circuit.
Accurate
amp
draw
readings
can
be
obtained
at
thermostat
subbase
terminals
R
and
W.
Fig.
15
illustrates
an
easy
method
of
obtaining
the
actual
amp
draw.
The
amp
reading
should
be
taken
after
the
blower
motor
has
started
and
the
furnace
is
operating
in
low
fire.
To
operate
the
furnace
in
low
fire,
first
move
SW2
to
ON
position,
THEN
close
R-WAVl,
with
ammeter
leads
connected
across
thermostat
subbase
R-W/Wl.
Return
SW2
to
final
desired
location
after
completing
the
reading.
NOTE:
When
using
an
electronic
thermostat,
set
the
cycle
rate
for
3
cycles
per
hr.
CHECK
SAFETY
CONTROLS
The
flame
sensor,
gas
valve,
and
pressure
switches
were
all
checked
in
the
Start-up
section
as
part
of
normal
operation.
17

Related product manuals