EasyManua.ls Logo

Carrier 100 Series - High Temperature and Special Gas Vent

Carrier 100 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
WARNING
When
this
furnace
is
converted
to
Category
III
it
must
have
its
own
dedicated
vent.
DO
NOT
common
vent
with
any
other
appliance.
Common
venting
with
other
appliances
will
result
in
spillage
of
flue
gas
and
failure
of
vent
system
which
may
cause
property
damage,
personal
injury,
or
death.
A
gaslight
heat
dissipator,
condensate
drain
tube
and
clamps,
condensate
trap
and
mounting
bracket,
and
draft
safeguard
modi¬
fication
plate
are
provided
in
the
kit.
No
substitution
for
any
of
the
components
may
be
made
when
installing
furnace
with
a
Category
III
vent
system.
Table
6—Vent
Pipe
Size*
HIGH-FIRE
INPUT
i
(BTUH)NORMAL
POSITION
PIPE
DIAMETER
40,000—84,000
3
in.
85,000—140,000
4
in.
*Only
Category
III
conversion
kit
specified
on
furnace
and
pipe
size
listed
for
furnace
Input
shall
be
used.
All
joints
in
the
vent
system,
between
vent
system
and
heat
dissipator,
and
between
heat
dissipator
and
furnace
must
be
sealed
airtight
with
only
the
high
temperature
RTV
specified
by
the
special
gas
vent
pipe
manufacturer.
The
accessory
kit
contains
provisions
for
vent
condensate
drainage.
Drain
and
trap
must
be
installed
per
kit
instructions.
Incorrect
drain
installations
may
cause
furnace
component
failure.
Furnace
installations
in
uncon¬
ditioned
spaces
where
temperature
may
fall
below
32°F
REQUIRE
freeze
protection
(heat
tape)
on
condensate
trap.
HIGH
TEMPERATURE
PLASTIC,
SPECIAL
GAS
VENT
IN¬
STALLATION
Cutting
1.
Hand
cut
piping
with
a
sharp
saw.
Saw
blade
must
have
at
least
24
teeth
per
in.
2.
Cut
pipe
squarely.
Use
of
a
miter
box
when
cutting
pipe
is
recommended.
NOTE:
DO
NOT
cut
with
power
saw.
Doing
this
may
cause
immediate
or
eventual
cracking
or
shattering
of
pipe.
DO
NOT
cut
or
alter
fittings.
Adhesive
Joining
Pipe
and
fittings
are
joined
together
using
high
temperature
RTV
adhesive/sealants.
Use
ONLY
adhesives
listed
by
vent
manufac¬
turer.
Do
not
use
any
other
adhesives
or
sealants.
Do
not
use
solvent
cements.
Do
not
drill
holes
in
pipe
or
fittings.
Do
not
use
sheet
metal
or
other
types
of
screws
to
join
plastic
piping
or
fittings.
Do
not
use
rivets
to
join
piping
or
fittings.
Before
applying
sealant,
pipe
ends
must
be
smooth
and
clean.
1.
Apply
minimum
1/4-in.
bead
of
adhesive/sealant
entirely
around
pipe
end
no
more
than
1/8-in.
from
end.
2.
Push
pipe
and
fitting
together
while
twisting
pipe
into
fitting.
3.
I
nspect
joint
for
complete
seal.
Full
curing
of
joints
takes
24
hr.
A
WARNING
Failure
to
ensure
complete
seal
of
all
joints
between
furnace,
heat
dissipator,
vent
pipes,
and
fittings
will
allow
spillage
of
flue
gas,
which
may
result
in
personal
injury
or
death.
Inspect
each
joint
after
the
adhesive/sealant
has
cured
to
ensure
that
all
joints
are
sealed.
Reapply
adhesive/sealant
to
any
joints
that
are
suspected
of
flue
gas
leakage.
Vent
Installation
Minimum
vent
length
is
5
ft
of
straight
pipe,
one
90°
long-radius
(sweep)
elbow
or
equivalent,
condensate
drain
assembly,
and
termination
(coupling
and
bird
screen).
Maximum
vent
length
is
40
ft
of
straight
pipe,
four
90°
long-radius
(sweep)
elbows,
condensate
drain
assembly,
and
termination
(coupling
and
bird
screen).
Length
and
number
of
elbows
may
be
adjusted
according
to
equivalent
ft
of
pipe
for
fittings
shown
in
Table
7.
Example:
If
adding
an
additional
90°
long-radius
(sweep)
elbow,
in
a
3-in.
diameter
vent
system,
maximum
vent
length
must
be
reduced
to
35
ft.
A
coupling
and
bird
screen
are
the
recommended
vent
termination
for
both
horizontal
and
vertical
vents.
If
a
tee
and
2
bird
screens
are
required
for
vertical
vents,
the
allowable
vent
length
must
be
adjusted
according
to
Table
7.
No
elbows
shall
be
used
as
terminations.
Table
7—Equivalent
Pressure
Drop
in
Length
of
Straight
Pipe
for
Fittings
FITTING
EQUIVALENT
FT
OF
PIPE
3-In.
Diameter
4-In.
Diameter
90°
Elbow
10
N/A
90°
Sweep
Elbow
(Long-
Radius)
5
6
45°
Elbow
5
5-1/2
Tee
Used
as
an
Elbow
10
10
Tee
Used
as
a
Termination
5
5
N/A—Not
applicable
All
horizontal
runs
of
piping
must
slope
backward
towards
drain
tee
1/4
in.
per
ft.
The
horizontal
run
between
the
drain
tee
and
the
furnace
must
also
slope
towards
the
drain
tee.
Vent
system
must
be
supported
at
least
every
5
ft
and
at
every
elbow
on
horizontal
runs.
Vertical
runs
must
be
supported
at
least
every
10
ft
by
supports
listed
by
vent
pipe
manufacturer.
Frame
opening
in
floor
using
lumber
which
is
dimensionally
consistent
with
structural
members.
Framing
must
be
level
and
must
provide
required
air
space
clearance
to
pipe.
Vertical
Vent
Termination
Where
vent
passes
through
roof,
a
listed
flashing
and
storm
collar
must
be
used
to
maintain
required
clearances
and
to
keep
weather
out.
Framed
opening
must
be
large
enough
to
maintain
required
air
clearance
taking
into
account
slope
of
roof.
Install
flashing
and
storm
collar
as
directed
by
vent
manufacturer.
Vertical
termination
must
be
at
least
2
ft
horizontally
from
roof
surface,
at
least
8
ft
away
from
any
vertical
wall,
and
must
extend
above
roof
as
required
in
kit
instructions.
Vents
extending
2-1/2
ft
or
more
above
roof
must
be
securely
guyed
or
braced
according
to
vent
manu¬
facturer’s
Installation
Instructions,
Terminate
with
a
coupling
and
a
bird
screen.
9

Related product manuals