EasyManua.ls Logo

Carrier 100 Series - Confined Space; Sides Special Gas Ventst Diameter; Vent Special Gas Ventst Diameter 3 3; Front Special Gas Ventst Diameter 3 3

Carrier 100 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For
Example:
58TUA
FURNACE
HIGH
FIRE
INPUT
BTUH
MINIMUM
SQ
FT
WITH
7-1/2
FT
CEILING
40,000
267
60,000
400
80,000
534
100,000
667
120,000
800
140,000
934
If
the
unconfined
space
is
of
unusually
tight
construction,
air
for
combustion
and
ventilation
MUST
come
from
either
the
outdoors
or
spaces
freely
communicating
with
the
outdoors.
Combustion
and
ventilation
openings
must
be
sized
the
same
as
for
a
confined
space
as
defined
below.
Return
air
must
not
be
taken
from
the
room
unless
an
equal
or
greater
amount
of
air
is
supplied
to
the
room,
CONFINED
SPACE
A
confined
space
MUST
have
2
permanent
openings,
1
within
12
in.
of
the
ceiling,
and
the
other
within
12
in.
of
the
floor.
(See
Fig.
2
.
)
NOTE:
In
determining
the
free
area
of
an
opening,
the
blocking
effect
of
the
louvers,
grilles,
and
screens
must
be
considered.
If
the
free
area
of
a
louver
or
grille
design
is
unknown,
it
may
be
assumed
that
wood
louvers
have
a
20
percent
free
area
and
metal
louvers
or
grilles
have
a
60
percent
free
area.
Screens,
when
used,
must
not
be
smaller
than
1/4-in.
mesh.
Louvers
and
grilles
must
be
constructed
so
they
cannot
be
closed.
The
size
of
the
openings
depends
upon
whether
the
air
comes
from
inside
or
outside
of
the
structure,
1.
All
air
from
inside
the
structure
Each
opening
MUST
have
at
least
1
square
in.
of
free
area
per
1000
Btuh
of
the
total
input
for
all
equipment
within
the
confined
space,
but
not
less
than
100
square
in,
per
opening.
(See
Fig.
2.)
The
minimum
dimension
of
air
openings
shall
be
not
less
than
3
in.
For
Example:
58TUA
FURNACE
HIGH
FIRE
INPUT
BTUH
FREE
AREA
OPEN¬
ING
(SQUARE
IN.)
40,000
100
60,000
100
80,000
100
100,000
100
120,000
120
140,000
140
If
the
building
is
constructed
unusually
tight,
a
permanent
opening
directly
communicating
with
the
outdoors
should
be
provided.
This
opening
shall
have
a
minimum
free
area
of
1
square
in.
per
5000
Btuh
of
total
input
rating
for
all
equipment
in
the
enclosure.
If
the
furnace
is
installed
on
a
raised
platform
to
provide
a
return-air
plenum,
and
return-air
is
taken
directly
from
the
hallway
or
space
adjacent
to
the
furnace,
all
air
for
combustion
must
come
from
outdoors,
2.
All
air
from
outdoors
SUPPLY
AIR
VENT
THROUGH
ROOF
(CATEGORY
I)
OR
WALL
(CATEGORY
III)
I
I
[
1
I
I
1
I
i
LJ12MAX
D
t
^
1
SO
IN.
M
PER
1000
BTUH*
INTERIOR
HEATED
SPACE
6
IN.
MIN
(FRONT)
t
1
SO
IN.
g
PER
1000
BTUH*
*
Minimum
opening
size
is
100
square
in.
with
minimum
dimensions
of
3
in.
I"
Minimum
of
3
in.
when
type-B
vent
is
used.
A89012
Fig.
2—Air
For
Combustion
and
Ventilation
(inside
Air)
a.
If
combustion
air
is
taken
from
outdoors
through
vertical
ducts,
the
openings
and
ducts
MUST
have
at
least
1
square
in.
of
free
area
per
4000
Btuh
of
the
total
input
for
all
equipment
within
the
confined
space.
(See
Fig.
3.)
For
Example:
58TUA
FURNACE
HIGH
FIRE
INPUT
BTUH
FREE
AREA
PER
OPENING
(SQUARE
IN.)
ROUND
PIPE
(IN.
DIA)
40,000
10.0
4
60,000
15.0
5
80,000
20.0
6
100,000
25.0
6
120,000
30.0
7
140,000
35.0
7
b.
If
combustion
air
is
taken
from
the
outdoors
through
horizontal
ducts,
the
openings
and
ducts
MUST
have
at
least
1
square
in.
of
free
area
per
2000
Btuh
of
the
total
input
for
all
equipment
within
the
confined
space.
(See
Fig.
3)
For
Example:
58TUA
FURNACE
HIGH
FIRE
INPUT
BTUH
FREE
AREA
PER
OPENING
(SQUARE
IN.)
ROUND
PIPE
(IN.
DIA)
40,000
20.0
6
60,000
30.0
7
80,000
40.0
8
100,000
50.0
8
120,000
60.0
9
140,000
70.0
10
When
ducts
are
used,
they
must
be
of
the
same
cross-sectional
area
as
the
free
area
of
the
openings
to
which
they
connect.
The
minimum
dimension
of
rectangular
ducts
must
not
be
less
than
3
in.
(See
Fig.
3.)
4

Related product manuals