EasyManua.ls Logo

Carrier 100 Series - Filter Arrangement; Leveling Legs; Gas Piping; Clearance

Carrier 100 Series
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
WARNING
Do
not
install
the
furnace
on
its
back
or
sides.
Safety
control
operation
will
be
adversely
affected.
Never
connect
return-air
ducts
to
the
back
of
the
furnace.
A
failure
to
follow
this
warning
can
cause
a
fire,
personal
injury,
or
death.
Step
3—FILTER
ARRANGEMENT
The
factory-supplied
filter(s)
is
shipped
in
the
blower
compart¬
ment.
Determine
location
for
the
filter
and
move
filter
retaining
hardware,
if
necessary,
before
attaching
the
return-air
duct.
After
the
return-air
duct
has
been
connected
to
the
furnace,
install
the
filter(s)
inside
the
furnace
blower
compartment.
See
Fig.
4
for
side
return
application
and
Fig.
5
for
bottom
return
application.
COMBINATIONS
OF
OPENINGS:
A&B
C&D
D&E
A89013
Fig.
3—Air
For
Combustion
and
Ventilation
(Outside
Air)
A
bottom
closure
panel
is
factory
installed
in
the
bottom
of
the
furnace.
When
bottom
return
inlet
is
desired,
remove
and
discard
the
enclosure
panel.
Filter-retaining
brackets,
supports,
and
retainers
are
factory
assem¬
bled
and
shipped
installed
for
side
return
application,
with
1
set
of
all
required
hardware
on
each
furnace.
(See
Fig.
4.)
For
bottom
return
applications,
remove
the
brackets
(front
and
back)
and
supports
from
each
side.
The
back
bracket(s)
are
installed
in
the
rear
of
the
furnace
casing
(dimples
are
provided
to
mark
mounting
screw
locations).
The
front
bracket(s)
are
installed
on
the
bottom
front
plate
as
shown
in
Fig.
5,
once
the
bottom
enclosure
has
been
removed.
Rotate
filter
supports
180°
so
filter
will
rest
on
support,
and
FILTER
RETAINER
SPRING
A93045
Fig.
4—Side
Filter
Arrangement
reinstall.
(Do
not
reinstall
in
17-1/2
in.
casing.)
Install
the
filter
retaining
rod
(small
U-shaped
end)
in
the
rear
bracket,
and
the
front
of
the
filter
retainer
rod
as
shown
in
Fig.
5.
Two
sets
of
hardware
are
needed
for
furnaces
in
24-1/2
in.
casings
using
2
filters
for
bottom
return.
All
hardware
is
provided
for
filter
installation.
NOTE:
Furnaces
with
a
17-1/2
in.
wide
casing
require
an
additional
procedure
when
locating
the
filter
for
bottom
return-air
application.
Field-fabricate
a
sheet
metal
filler
strip
1
X
3
X
24-1/2
in.
and
install
it
along
side
of
the
filter
as
shown
in
Fig.
5.
Drive
2
screws
through
the
casing
side
and
into
the
filler
strip
to
secure
it
in
place.
Filter
is
to
rest
on
top
of
the
filler
strip
when
installed.
Table
3—Filter
Information
(In.)
FURNACE
FILTER
SIZE*
FILTER
CASING
WIDTH
Side
Return
Bottom
Return
TYPE
14-3/16
(1)
16
X
25
X
It
(1)
14X25X1
Cleanable
17-1/2
(1)
16
X
25
X
It
(1)
16X25X1
Cleanable
21
(1)
16X25X
1
{1)20X25X
1t
Cleanable
24-1/2
(2)
16X25
X
It
(1)24X25X1
Cleanable
*FiIters
can
be
field-modified
by
cutting
the
frame
as
marked
and
folding
to
the
desired
size.
Alternate
sizes
can
be
ordered
from
your
distributor
or
dealer.
tFactory
provided
with
the
furnace.
A
WARNING
Never
operate
unit
without
a
filter
or
with
filter
access
door
removed.
A
failure
to
follow
this
warning
can
cause
a
fire,
personal
injury,
or
death.
Step
4—LEVELING
LEGS
(If
Required)
When
the
furnace
is
used
with
side
inlet(s)
and
leveling
legs
are
required,
refer
to
Fig.
6
and
install
field-supplied
corrosion-
resistant
5/16-in.
machine
bolts
and
nuts.
NOTE:
The
length
of
the
bolt
should
not
exceed
1-1/2
in.
1.
Lay
furnace
on
its
back,
locate
and
drill
5/16-in.
diameter
hole
in
each
bottom
comer
of
furnace
as
shown
in
Fig.
6.
2.
Install
nut
on
bolt
and
install
bolt
and
nut
in
hole.
(Install
flat
washer
if
desired.)
3.
Install
another
nut
on
other
side
of
furnace
base.
(Install
flat
washer
if
desired.)
4.
Adjust
outside
nut
to
provide
desired
height,
and
tighten
inside
nut
to
secure
anangement.
Step
5—GAS
PIPING
Gas
piping
must
be
installed
in
accordance
with
national
and
local
codes.
Refer
to
the
current
edition
of
the
National
Fuel
Gas
Code.
5

Related product manuals