33
0
Resettable
Fault
203 Fiber Offline 0
Fiber online to offline 0. The fiber-optic
communication link between the main
control board and M0 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M0 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
204 Fiber Offline 1
Fiber online to offline 1. The fiber-optic
communication link between the main
control board and M1 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M1 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
205 Fiber Offline 2
Fiber online to offline 2. The fiber-optic
communication link between the main
control board and M2 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M2 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
206 Fiber Offline 3
Fiber online to offline 3. The fiber-optic
communication link between the main
control board and M3 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M3 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
207 Fiber Offline 4
Fiber online to offline 4. The fiber-optic
communication link between the main
control board and M4 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M4 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
208 Fiber Offline 5
Fiber online to offline 5. The fiber-optic
communication link between the main
control board and M5 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and M5 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE