34
0
Resettable 
Fault
209 Fiber Offline 6
Fiber online to offline 6. The fiber-optic 
communication link between the main 
control board and M6 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and M6 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
0
Resettable 
Fault
210 Fiber Offline 7
Fiber online to offline 7. The fiber-optic 
communication link between the main 
control board and M7 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and M7 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
0
Resettable 
Fault
211 Fiber Offline 8
Fiber online to offline 8. The fiber-optic 
communication link between the main 
control board and M8 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and M8 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
0
Resettable 
Fault
212 Fiber Offline 9
Fiber online to offline 9. The fiber-optic 
communication link between the main 
control board and M9 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and M9 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
0
Resettable 
Fault
213 Fiber Offline 10
Fiber online to offline 10. The fiber-optic 
communication link between the main 
control board and L0 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and L0 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
0
Resettable 
Fault
214 Fiber Offline 11
Fiber online to offline 11. The fiber-optic 
communication link between the main 
control board and L1 PLI transitioned 
from online to offline.
Power down and then check the fiber-
optic communication connection 
between the fiber interface circuit board 
and L1 PLI for damage. Replace the 
fiber-optic cable and/or fiber transceiver 
circuit board if needed. See the 
hardware service manual, publication 
750-TG100 for PowerFlex 755T or 
publication 750-TG101 for PowerFlex 
755TS products, for the replacement 
procedure. See the control pod fiber 
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop 
(Line Side Converter). Additional 
Fault Action. Fault opens main circuit 
breaker: Yes. Fault can automatically 
reset: No. Emergency override 
response: Cannot override this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE