35
0
Resettable
Fault
215 Fiber Offline 12
Fiber online to offline 12. The fiber-optic
communication link between the main
control board and L2 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L2 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
216 Fiber Offline 13
Fiber online to offline 13. The fiber-optic
communication link between the main
control board and L3 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L3 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
217 Fiber Offline 14
Fiber online to offline 14. The fiber-optic
communication link between the main
control board and L4 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L4 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
218 Fiber Offline 15
Fiber online to offline 15. The fiber-optic
communication link between the main
control board and L5 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L5 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
219 Fiber Offline 16
Fiber online to offline 16. The fiber-optic
communication link between the main
control board and L6 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L6 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
0
Resettable
Fault
220 Fiber Offline 17
Fiber online to offline 17. The fiber-optic
communication link between the main
control board and L7 PLI transitioned
from online to offline.
Power down and then check the fiber-
optic communication connection
between the fiber interface circuit board
and L7 PLI for damage. Replace the
fiber-optic cable and/or fiber transceiver
circuit board if needed. See the
hardware service manual, publication
750-TG100 for PowerFlex 755T or
publication 750-TG101 for PowerFlex
755TS products, for the replacement
procedure. See the control pod fiber
diagram on the Tables & Graphics tab.
Coast (Motor Side Inverter). Stop
(Line Side Converter). Additional
Fault Action. Fault opens main circuit
breaker: Yes. Fault can automatically
reset: No. Emergency override
response: Cannot override this fault.
Table 7 — Fault Codes by Port (cont)
PORT
CONDITION
DISPLAY
TEXT
FAULT ACTION FAULT ACTION
TYPE CODE

Table of Contents