17

The power cables can enter the 30XW control box from
above the unit. A removable aluminium plate on the upper
part of the control box face allows introduction of the cables.
Refer to the certied dimensional drawing for the unit.

IMPORTANT: Field connection of interface circuits may
lead to safety risks: any control box modication must
maintain equipment conformity with local regulations.
Precautions must be taken to prevent accidental electrical
contact between circuits supplied by different sources:
The routing selection and/or conductor insulation
characteristics must ensure dual electric insulation.
In case of accidental disconnection, conductor xing
between different conductors and/or in the control
box prevents any contact between the conductor ends
and an active energised part.
Refer to the 30XA/30XW Pro-Dialog Control manual and
the certied wiring diagram supplied with the unit for the
eld control wiring of the following features:
Remote on/off switch
Demand limit external switch
Remote dual set point
Alarm, alert and operation report
Evaporator pump control
Heat reclaim condenser pump control (option)
Hot water valve control (option)
Various interlocks on the Energy Management Module
(EMM) board (accessory or option)
CCN bus connection
The permanent connection to the system CCN bus is
made at the terminal provided for this purpose inside
the control box.
The connection of the CCN service tool is possible at a
socket under the control box, accessible from outside.









       
  

254 - 304 1 x 150 1 x 50 160 XLPECu 1 x 95 310 PVCCu
354 1 x 240 1 x 70 220 XLPECu 1 x 95 350 PVCCu
402 1 x 240 1 x 70 170 XLPECu 1 x 150 350 PVCCu
452 - 512 1 x 240 1 x 95 230 XLPECu 1 x 185 390 PVCCu
552 - 562 - 602 1 x 240 1 x 95 275 XLPECu 1 x 185 360 PVCCu
652 - 712 1 x 240 1 x 120 210 XLPECu 1 x 240 380 PVCCu
702 - 812 1 x 240 1 x 150 230 XLPECu 1 x 240 330 XLPECu
802 - 852 - 862 1 x 240 1 x 150 217 XLPECu 1 x 240 320 XLPECu
1002 2x240/2x240 1x95/1x95 200/200 XLPECu 1x240/1x240 400/400 PVCCu
1012 2x240/2x240 1x120/1x95 230/200 XLPECu 1x240/1x240 400/401 PVCCu
1052 - 1154 - 1162 2x240/2x240 1x120/1x120 220/220 XLPECu 2x120/2x120 375/375 PVCCu
1252 - 1314 2x240/2x240 1x150/1x120 220/220 XLPECu 2x185/2x120 410/375 PVCCu
1352 - 1464 2x240/2x240 1x150/1x150 220/220 XLPECu 2x185/2x185 410/410 PVCCu
1452 - 1612 2x240/2x240 1x185/1x185 230/230 XLPECu 2x185/2x185 370/370 PVCCu
1552 - 1702 - 1762 2x240/2x240 1x185/1x185 220/220 XLPECu 2x240/2x240 400/400 PVCCu
1652 2x240/2x240 1x185/1x185 220/230 XLPECu 2x240/2x185 400/400 PVCCu

254 - 304 1 x 240 1 x 70 190 XLPECu 1 x 150 370 PVCCu
354 1 x 240 1 x 70 170 XLPECu 1 x 185 400 PVCCu
402 1 x 240 1 x 95 190 XLPECu 1 x 240 420 PVCCu
452 - 512 1 x 240 1 x 120 210 XLPECu 1 x 185 290 PVCCu
552 - 562 - 602 1 x 240 1 x 120 210 XLPECu 1 x 240 340 XLPECu
652 - 712 2 x 240 1 x 240 275 XLPECu 2 x 150 320 XLPECu
702 - 812 2 x 240 1 x 240 250 XLPECu 2 x 150 300 XLPECu
802 - 852 - 862 2 x 240 2 x 240 240 XLPECu 2 x 150 280 XLPECu
1002 2x240/2x240 1x150/1x150 220/230 XLPECu 2x150/2x150 310/340 PVCCu
1012 2x240/2x240 1x150/1x150 220/220 XLPECu 2x185/2x185 410/410 XLPECu
1052 - 1154 - 1162 2x240/2x240 1x150/1x150 210/210 XLPECu 2x185/2x185 400/400 PVCCu
1252 - 1314 2x240/2x240 1x240/1x150 240/210 XLPECu 2x185/2x185 310/400 XLPECu/PVCCu
1352 - 1464 2x240/2x240 1x240/1x240 240/240 XLPECu 2x185/2x185 310/310 XLPECu
1452 - 1612 2x240/2x240 2x120/2x120 220/220 XLPECu 2x240/2x185 320/310 XLPECu
1552 - 1652 - 1702 - 1762 2x240/2x240 2x120/2x120 210/210 XLPECu 2x240/2x240 320/320 XLPECu

 4 x 240 2 x 150 220 XLPECu 4 x 120 375 PVCCu
 4 x 240 4 x 120 210 XLPECu 4 x 240 400/400 PVCCu

 4 x 240 2 x 185 220 XLPECu 4 x 150 310 XLPECu
 5 x 240 4 x 120 210 XLPECu 4 x 240 320 XLPECu
* Connectioncapacitiesactuallyavailableforeachmachine,denedaccordingtotheconnectionterminalsize,thecontrolboxaccessopeningsizeandtheavailable
spaceinsidethecontrolbox.
** Selectionsimultationresultconsideringthehypothesisindicated.
*** IfthemaximumcalculatedsectionisforanXLPEcabletype,thismeansthataselectionbasedonaPVCcabletypecanexceedtheconnectioncapacityactually
available.Specialattentionmustbegiventotheselection.
Thecurrentsconsideredaregivenforamachineequippedwithahydraulicmoduleoperatingatmaximumcurrent.