Carrier 30XW - Unit Options and Features; Master;Slave and Heat Reclaim

Carrier 30XW
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30

    

Medium-temperaturebrine
solution
5 Implementationofnewcontrolalgorithmsandredesigned
evaporatortoallowchilledbrinesolutionproductiondownto-6°C
whenethyleneglycolisused(-3°Cwithpropyleneglycol)
Coversspecicapplicationssuchasicestorageand
industrial processes
Only sizes
512/562/1012/1154
Low-temperaturebrinesolution 6 Implementationofnewcontrolalgorithmsandredesigned
evaporatortoallowchilledbrinesolutionproductiondownto-12°C
whenethyleneglycolisused(-8°Cwithpropyleneglycol)
Coversspecicapplicationssuchasicestorageand
industrial processes
Only sizes
512/562/1012/1154
Light-brinesolution,downto
-3°C
8 Implementationofnewcontrolalgorithmsandredesigned
evaporatortoallowchilledbrinesolutionproductiondownto-3°C
whenethyleneglycolisused(0°Cwithpropyleneglycol)
Matches with most application requirements for
ground-sourcedheatpumpsandtswithmany
industrial processes requirements
254-1762
Unitsuppliedintwoassembled
parts
51 Theunitisequippedwithangesthatallowdisassemblyoftheunit
on site
Facilitates installation in plant rooms with limited access Only sizes
1612/1652/1702/1762
Master/slaveoperation 58 Unitequippedwithsupplementarywateroutlettemperaturesensor
kit(tobeeldinstalled)allowingmaster/slaveoperationoftwo
units connected in parallel
Optimised operation of two units connected in parrallel
operation with operating time equalisation
254-1762
Single power connection point 81 Unitpowerconnectionviaonemainsupplyconnection Quick and easy installation 1002-1762
No disconnect switch 82A Unitwithoutdisconnectswitch,butwithshort-circuitprotection
device
Permits an external electrical disconnect system for the
unit(eld-supplied),whileensuringunitshortcircuit
protection
254-1762
Evap.singlepumppower/control
circuit
84 Unitequippedwithanelectricalpowerandcontrolcircuitforone
pump evaporator side
Quickandeasyinstallation:thecontrolofxedspeed
pumpsisembeddedintheunitcontrol
254-1252, 1314
Evap.dualpumpspower/control
circuit
84D Unitequippedwithanelectricalpowerandcontrolcircuitfortwo
pumps evaporator side
Quickandeasyinstallation:thecontrolofxedspeed
pumpsisembeddedintheunitcontrol
254-1252, 1314
Cond.singlepumppower/control
circuit
84R Unitequippedwithanelectricalpowerandcontrolcircuitforone
pump condenser side
Quickandeasyinstallation:thecontrolofxedspeed
pumpsisembeddedintheunitcontrol
254-1252, 1314
Condenser insulation 86 Thermalcondenserinsulation Minimizes thermal dispersions condenser side (key
option for heat pump or heat recovery applications)
254-1762
Service valve set 92 Liquid line valve (evaporator inlet) and compressor suction line
valve
Allow isolation of various refrigerant circuit components
forsimpliedserviceandmaintenance
254-1762
Evaporator with one pass less 100C Evaporatorwithonepassonthewaterside.Evaporatorinletand
outletonoppositesides.
Easytoinstall,dependingonsite.Reducedpressure
drops
254-1762
Condenser with one pass less 102C Condenserwithonepassonthewaterside.Condenserinletand
outletonoppositesides.
Easytoinstall,dependingonsite.Reducedpressure
drops
254-1762
21barevaporator 104 Reinforced evaporator for extension of the maximum water-side
servicepressureto21bar(standard10bar)
Covers applications with a high water column evaporator
side(typicallyhighbuildings)
254-1762
21barcondenser 104A Reinforced condenser for extension of the maximum water-side
servicepressureto21bar(standard10bar)
Covers applications with a high water column condenser
side(typicallyhighbuildings)
254-1762
Reversed evaporator water
connections
107 Evaporatorwithreversedwaterinlet/outlet Easyinstallationonsiteswithspecicrequirements 254-1762
Reversed condenser water
connections
107A Condenserwithreversedwaterinlet/outlet Easyinstallationonsiteswithspecicrequirements 254-1762
J-Bus gateway 148B Bi-directionalcommunicationboardcomplyingwithJBusprotocol Connectstheunitbycommunicationbustoabuilding
management system
254-1762
Lon gateway 148D Bi-directionalcommunicationboardcomplyingwithLonTalk
protocol
Connectstheunitbycommunicationbustoabuilding
management system
254-1762
BacnetoverIP 149 Bi-directional high-speed communication using BACnet protocol
overEthernetnetwork(IP)
Easyandhigh-speedconnectionbyethernetlinetoa
buildingmanagementsystem.Allowsaccesstomultiple
unit parameters
254-1762
High condensing temperature 150 Optimized compressor for operation at high condensing
temperature
Increasedcondenserleavingwatertemperatureupto
63°C.Allowsapplicationswithhighcondensing
temperature (heat pumps, installations with not
generously sized dry-coolers or more generally,
installationswithdry-coolersinhotclimate).NOTE:to
ensure control of the condenser leaving water
temperature,thisoptionmustbettedontheunits.
30XWH-/XW-P/
XWHP254-1762&
30XW--0254/0304/354
Condensing temperature
limitation
150B Limitation of the maximum condenser leaving water temperature to
45°C
Reducedmaximumpowerinputandcurrentabsorption:
powercablesandprotectionelementscanthereforebe
downsized
254-1762
Controlforlowcond.
temperature
152 Outputsignal(0-10V)tocontrolthecondenserwaterinletvalve Simple installation: for applications with cold water at
condenserinlet(ex.ground-source,groundwater-
source,supercialwater-sourceapplications)thesignal
permits to control a 2 or 3-way valve to maintain
condenser water temperature (and so condensing
pressure)atacceptablevalues
254-1762
Energy Management Module 156 EMMControlboardwithadditionalinputs/outputs.SeeEnergy
Management Module option chapter
Extendedremotecontrolcapabilities(Set-pointreset,
icestorageend,demandlimits,boileron/o
command...)
254-1762
7" user interface 158A Control supplied with a 7 inch colour touch screen user interface Enhancedeaseofuse. 254-1762
InputcontactforRefrigerantleak
detection
159 0-10Vsignaltoreportanyrefrigerantleakageintheunitdirectlyon
thecontrolller(theleakdetectoritselfmustbesuppliedbythe
customer)
Immediatecustomernoticationofrefrigerantlossesto
the atmosphere, allowing timely corrective actions
254-1762
Compliance with Swiss
regulations
197 Additional tests on the water heat exchangers: supply (additional
ofPEDdocuments)supplementarycerticatesandtest
certications
Conformance with Swiss regulations 254-1762
Compliance with Australian
regulations
200 UnitapprovedtoAustraliancode Conformance with Australian regulations 254-1762
Low noise level 257 Evaporator sound insulation 3 dB(A) quiter than standard unit 254-1762
Welded evaporator connection
kit
266 Victaulicpipingconnectionswithweldedjoints Easy installation 254-1762
Welded condenser water
connection kit
267 Victaulicpipingconnectionswithweldedjoints Easy installation 254-1762
Flanged evaporator water
connection kit
268 Victaulicpipingconnectionswithangedjoints Easy installation 254-1762
Flanged condenser water
connection kit
269 Victaulicpipingconnectionswithangedjoints Easy installation 254-1762
Thermalcompressorinsulation 271 Thecompressoriscoveredwithathermalinsulationlayer Prevents air humidity to condensate on the compressor
surface
254-1762
230Velectricalplug 284 230VACpowersupplysourceprovidedwithplugsocketand
transformer(180VA,0,8Amps)
Permits connection of a laptop or an electrical device
during unit commissioning or servicing
254-1762
Carrier Connect link (only
Europeandistribution
companies)
298 3GrouterboardNOTE1:requireoption149
NOTE2:whenmorethanonemachineisinstalledonsite,only
oneofthemshallbeequippedwithoption298whileallofthem
mustbeequippedwithoption149NOTE3:iftheCarrier®
PlantCTRL™isonsite,option298shallbeintegratedinthe
Carrier®PlantCTRL™whileoption149isstillmandatoryforeach
singleunit.
EnablerforCarrierConnectserviceoer 254-1762