Page 9.5
Using the Dehum TerminalUsing the Dehum Terminal
Press the HUMIDITY button to leave the Setup screens. If no buttons are 
pressed, the display will leave the setup screens after 30 seconds.
HUMIDITY
Press
Normally Closed (NC) = 
  DEHUM de-energized for 
  low speed fan.
Normally Open (NO) = 
  DEHUM energized for 
  low speed fan.
 
NC
NO
DeHumidify
Setup
I0
If you configure a MISC output jumper for DEHUM, it may be 
programmed to operate in one of two ways: 
 
 
  1) Normally Closed (NC):  The thermostat will de-energize the 
       DEHUM terminal to allow the fan to run in low speed when there 
       is a call for 1st stage cooling and the room humidity is greater than 
       the dehumidification setpoint.  
  2) Normally Open (NO):  The thermostat will energize the DEHUM 
       terminal to allow the fan to run in low speed when there is a call 
       for 1st stage cooling only and the room humidity is greater 
       than the dehumidification setpoint.
 
Dehumidification Notes: The DEHUM terminal will “release” and allow 
the fan to operate normally if there is call for 2nd stage cooling or if the call 
for Cooling and/or Cool to Dehumidify has been satisfied.  
Note: Press the MODE 
button momentarily 
to move through the 
setup screens.  Press 
and hold the MODE 
button to move back- 
wards through the 
setup screens.
HUMIDITY
MODE
MODE
Press the MODE button.  While holding 
the MODE, press the HUMIDITY button 
to enter Setup screens.
Press the MODE button repeatedly 
until this setup screen appears.
9