Table 3 - 38VMA072, 096, 120,144HDS 
No. in refrigerant 
system diagram 
Symbol  Name  Major Function 
A  INV  Inverter compressor 
Inverter compressor is operated on frequencies between 20 Hz and 100 Hz. 
B  INV1  Inverter compressor 
C    Heat exchanger  To exchange heat with ambient environment. 
D  FAN A  Left Inverter fan  The fan is operated at 13-step rotation speed by using the inverter. 
E  FAN B  Right Inverter fan  The fan is operated at 13-step rotation speed by using the inverter. 
F  EXV A  Electronic expansion valve  Used to adjust refrigerant volume. 
G  EXV B  Electronic expansion valve  Used to adjust refrigerant volume. 
H  EXV C  Electronic expansion valve  Used to adjust sub-cooling. 
I  PHE  Plate Heat Exchanger  Used for sub-cooling liquid refrigerant from the electronic expansion valve. 
J  SV4  Solenoid valve  Used to balance the oil between modules. 
K  SV7  Solenoid valve 
This valve opens at a pressure of 565.6 psi to prevent pressure from 
increasing. 
L  ST1  4-way valve  Used to switch the operation mode between cooling and heating. 
M  H-LY1  High pressure sensor  Used to detect high pressure. 
N  L-LY1  Low pressure sensor  Used to detect low pressure. 
O  H-PRO  High pressure switch 
Used to protect the system pressure. When system pressure is too high, the 
pressure switch will open. Once the pressure switch is open, compressor 
will stop and will restart after 12 minutes. 
P  L-PRO  Low pressure switch 
Used to protect the system pressure. When the system pressure is too low, 
the pressure switch will open. Once the pressure switch is open, 
compressor will stop, and will restart after 12 minutes. 
Q    Pressure regulating valve 
This valve opens at a pressure of 580 psig to prevent pressure from 
increasing, thus resulting in no damage to functional parts due to the 
increase of pressure in transportation or storage. 
R    Oil separator 
Used to separate oil from high pressure and high temperature refrigerant, 
which is pumped out during compression. 
S    Accumulator 
Used to store the liquid refrigerant and oil. It can protect the compressor 
from liquid slugging. 
T  T3  Thermistor (outdoor coil deicer) 
Used to detect liquid pipe temperature of ODU heat exchanger, determine 
defrosting operation, and others. 
1  T4  Thermistor (Outdoor air)  Used to detect outdoor / ambient temperature. 
2  T5  Thermistor (liquid pipe)  Detects temperature of liquid pipe after Plate Heat Exchanger. 
3  T6 
Thermistor (Plate Heat 
Exchanger gas pipe) 
Detects temperature of gas pipe on the evaporation side of Plate Heat 
Exchanger. Used to maintain constant control on superheated of the Plate 
4  T7  Thermistor (Accumulator outlet)  Used to detect gas pipe temperature at the accumulator outlet. 
5  INV Gas  Thermistor (INV discharge pipe) 
Used to detect discharge pipe temperature. Enables the temperature 
protection control of compressor, and others. 
6  INV1 Gas  Thermistor (INV1 discharge pipe) 
Used to detect discharge pipe temperature. Enables the temperature 
protection control of compressor, and others. 
 
 
 
 
   
10