Table 32 - List of Advanced Mode Codes 
Symbol  Function  Item  Description 
_n1_  Special function for debug 
_n12 
Forced cooling (62.6
F of IDU) 
_n13 
Forced heating (86
F of IDU) 
_n14  Cooling test 
_n15  Heating test 
_n2_  Refrigerant recycle function 
_n21  Refrigerant recycle to outdoor units 
_n22  Refrigerant recycle to indoor units 
_n23  Refrigerant recycle to piping 
_n26  Maintenance operation 
_n3_  Error query 
_n31  Historical error query 
_n32  Clear the historical errors 
_n4_  Night time setting 
_n41  6/10h (default) 
_n42  6/12h 
_n43  8/10h 
_n44  8/12h 
_n5_  Silent mode setting 
_n51  Night silent mode 
_n52  Silent mode 
_n53  Super silent mode 
_n54  None silent mode (default) 
_n8_  Static pressure mode setting 
_n81  Standard static pressure mode (Default) 
_n82  Low static pressure mode (Reserved) 
_n83  Medium static pressure mode (Reserved) 
_n84  High static pressure mode (Reserved) 
_nb_  Temperature unit setting 
_nb1  Temperature unit: °C 
_nb2  Temperature unit: °F (Default) 
_NC_ 
T4 sensor (outdoor temperature) threshold 
to enable Auxiliary Heat. Aux heat will 
enable when outdoor temperature falls 1.8 F 
below this temperature. 
_nC1  Auxiliary heat disabled 
_nC2  5°F 
_nC3  15°F 
_nC4  25°F 
_nC5  35°F 
_nC6  45°F 
_nC7  55°F 
_nC8  65°F 
NOTE: All codes are only available for master unit. 
a.  Instruction for Advanced Mode 
Special function for debug: 
_n12” Forced Cooling 
Enter “Forced cooling (_n12)” mode. All indoor units will run in cooling mode,  and the forced cooling mode will be exited 
automatically after running 60 minutes. 
_n13” Forced Heating 
Enter “Force heating  (_n13)”mode.  All indoor units will run in  heating mode,  and the forced heating mode will be  exited 
automatically after running 60 minutes. 
   
40