b.  Refrigerant Recycling Operation 
_n21” Refrigerant recycles to outdoor units 
1.  Close the liquid stop valve. 
2.  Enter “Refrigerant recycle to outdoor units (_n21)” mode. 
3.  Let the unit run for a while, and then close the gas valve quickly. 
_n22” Refrigerant recycles to indoor units 
1.  Close the liquid stop valve. 
2.  Enter “Refrigerant recycle to indoor units (_n22)” mode. 
3.  Let the unit run for a while, and then close the gas valve quickly. 
_n23” Refrigerant recycled to piping 
Enter “Refrigerant recycle to piping (_n23)” mode and all indoor valves will open. 
c.  Snow-Blowing Function 
1.  Press SW5 button on spot check box of the header outdoor unit to enter the snow-blowing function.   
It will display
Sn0” for 15 seconds. 
2.  Press SW5 button again to exit the snow-blowing function. 
It will display “Sn1” for 15 seconds. 
The snow-blowing modes can be selected through S11 dip switch on spot check box. 
Mode  Heavy Snow Mode  Light Snow Mode 
S11 
If the unit receives a startup signal, it will exit the snow-blowing function. 
   
41