Table 15 - EXV A, EXV B (38VMA144HDS) 
Capacity  1—15  16—30  31—48 
Initial pulse step  120P  250P  380P 
Normal control 
 
 
 
Table 16 - EXV C   
Electronic Expansion Valve  EXV C 
Normal control  0P 
NOTE:   
Completely open position of electronic expansion valve (EXV) is 480P. 
When the compressor ramps up, EXV will be at initial pulse step for 4 minutes, and then the EXV will be adjusted according to 
the maximum discharge temperature.   
The system will check the maximum discharge temperature every 2 minutes. 
4. Fan Control 
Table 17 - Fan Steps 
Fan Steps 
Rotating Speed 
38VMA072, 096HDS  38VMA120HDS  38VMA144HDS 
0  0 / 0  0 / 0  0 / 0 
1  250 / 0  250 / 0  250 / 0 
2  330 / 0  330 / 0  330 / 0 
3  250 / 250  250 / 250  250 / 250 
4  330 / 330  330 / 330  330 / 330 
5  410 / 410  410 / 410  410 / 410 
6  460 / 460  460 / 460  460 / 460 
7  530 / 530  530 / 530  530 / 530 
8  580 / 580  580 / 580  580 / 580 
9  660 / 660  660 / 660  660 / 660 
10  710 / 710  710 / 710  710 / 710 
11  760 / 760  800 / 800  800 / 800 
12 (standard 0pa)  800 / 800  850 / 850  980 / 890 
13 (20pa)  870 / 870  870 / 870  980 / 890 
14 (40pa)  980 / 890  980 / 890  980 / 890 
15 (60pa)  1010 / 930  1010 / 930  1010 / 930 
 
 
   