a. 0E0: Communication Fault Between ODUs
1. Error display:
ODU display: 0E0
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error Definition
Communication error between header unit and follower unit (display on follower unit).
4. Possible causes:
Incorrect address setting of ODU
Communication lines between ODUs is not installed correctly
Wiring between main board and communication adapter is not installed correctly
Damaged main board or communication terminal block of ODU
Figure 35 - Communication Terminal Block of ODU