EasyManua.ls Logo

Carrier 38VMA Series - 0 H7: Incorrect Number of IDUs

Carrier 38VMA Series
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
i. 0H7: Incorrect Number of IDUs
1. Error display:
ODU display: 0H7
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error definition:
The number of physically connected indoor units to an outdoor unit does not match the ENC3 + S12 setting.
4. Possible causes:
Incorrect number of IDUs set for the main board of the ODU
Duplicated addresses exist for the IDUs in the system
IDU power is OFF
The communication line between IDU and ODU or some IDUs are installed incorrectly
Damaged individual main board of IDU
Damaged main board of ODU