g.  0H1: Communication Error Between Main Control Chip and Communication Chip 
1.  Error display:   
ODU display: 0H1   
2.  Applicable models:   
38VMA***HDS5-1 (208/230V-3Ph-60Hz) 
38VMA***HDS6-1 (460V-3Ph-60Hz) 
3.  Error definition: 
Communication fault of main control chip IC55 and communication chip IC33 on main board. 
4.  Possible causes:   
•  Improper power supply 
•  Damaged transformer 
•  Damaged main board 
 
h.  0H2~0H3: Incorrect Number of ODUs 
1.  Error display: 
ODU display: 0H2 or 0H3 (displayed on header unit only) 
2.  Applicable models:   
38VMA***HDS5-1 (208/230V-3Ph-60Hz) 
38VMA***HDS6-1 (460V-3Ph-60Hz) 
3.  Error definition:   
0H2 -- The number of physical connected follower units to master unit is less than ENC1 rotary switch setting. 
0H3 -- The number of physical connected follower units to master units is more than ENC1 rotary switch setting. 
4.  Possible causes:   
•  Improper power supply for ODU 
•  Duplicated address setting for ODU 
•  Communication lines between ODUs are installed incorrectly 
•  Damaged communication terminal block or main board for ODU 
 
48