q. 0P1: Discharge Temperature Switch or High Pressure Protection
1. Error display:
ODU display: 0P1
2. Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3. Error definition:
Operation of discharge temperature switch (the detected discharge temperature > 239 °F)
The detected pressure of high pressure sensor > 565.6 psi
4. Possible causes:
High pressure due to excess refrigerant in the system
High compressor discharge temperature caused by lack of refrigerant in the system
Damaged main board
Improper operation of sub-cooler valve resulting in the loss of cooling function
Low pressure resulted due to refrigerant blockage on high pressure side resulting in solenoid valve error (IDU, ODU)
Improper operation of relief valve on the refrigerant system due to the solenoid valve error (IDU, ODU)
The high pressure is too high and the low pressure is too low because of blockage in the system