6
AHRI* CAPACITY RATINGS
Model Numbers Cooling
High Heating
47° F (8.33° C)
Low Heating
17° F ( --- 8.33° C)
Outdoor Unit Indoor Unit
Capacity
(Btuh)
EER SEER Capacity (Btuh) HSPF Capacity (Btuh)
3 8G VM 2 1 8 --- --- --- 3
2 x 4 0 G V M0 09 --- --- --- 3 18,000 10.2 16.0 19,000 8.2 9,600
4 0G VM 0 0 9 --- --- --- 3
+ 4 0G V M 0 1 2 --- --- --- 3
18,000 10.2 16.0 19,000 8.2 9,600
3 8G VM 2 2 4 --- --- --- 3
2 x 4 0 G V M0 09 --- --- --- 3
+ 4 0G V M 0 1 2 --- --- --- 3
26,000 8.2 16.0 29,000 8.2 17,000
3 x 4 0 G V M0 09 --- --- --- 3 26,000 8.2 16.0 29,000 8.2 17,000
4 0G VM 0 0 9 --- --- --- 3 +
2 x 4 0 G V M0 12 --- --- --- 3
26,000 8.2 16.0 29,000 8.2 17,000
3 8G VM 4 3 0 --- --- --- 3
4 x 4 0 G V M0 09 --- --- --- 3 29,000 7.3 16.0 30,400 8.2 16,500
4 0G VM 0 0 9 --- --- --- 3 +
2 x 4 0 G V M0 12 --- --- --- 3
+ 4 0G V M 0 1 8 --- --- --- 3
29,000 7.3 16.0 30,400 8.2 16,500
3 8G VM 4 3 6 --- --- --- 3 N on --- D u ct ed F C U ’ s 34,400 8.0 16.0 37,200 8.2 22,000
3 8G VM 5 4 2 --- --- --- 3 N on --- D u ct ed F C U ’ s 40,000 9.3 16.0 43,000 8.0 24,800
*Air Conditioning, Heating & Refrigeration Institute
--- --- = N / A
Legend
EER --- Energy Efficiency Ratio
HSPF --- Heating Seasonal Performance Factor
SEER --- Seasonal Energy Efficiency Ratio
NOTES:
1. Ratings are net values reflecting the effects of circulating fan heat. Ratings are based on: Cooling Standard: 80_F (26.67_C) db, 67_F (19.44_C) wb air entering indoor unit and 95_F
(35_C) db air entering outdoor unit. High Temperature Heating Standard: 70_F (21.11_C) db air entering indoor unit and 47_F (8.33_C) db, 43_F (6.11_C) wb air entering outdoor
unit.
2. Ratings are based on 25 ft. (7.62 m) of interconnecting refrigerant lines.
3. All system ratings are based on fan coil units operating at high fan speed. Consult Physical Data tables for air flows at all available fan speeds.
AIR THROW DATA
Model Number
Approximate Air Throw ft. (m)
Low Medium High Turbo
4 0G VM 0 0 9 --- --- --- 3 18 (5.5) 21 (6.4) 24 (7.3) 27 (8.2)
4 0G VM 0 1 2 --- --- --- 3 19 (5.8) 21 (6.4) 24 (7.3) 27 (8.2)
4 0G VM 0 1 8 --- --- --- 3 25 (7.6) 29 (8.8) 32 (9.8) 35 (10.7)
SOUND RATINGS
Outdoor
Units
Model Number
Sound Power dBA Sound Pressure dBA
3 8G VM 2 1 8 --- --- --- 3 ( c oo l / h e a t ) 66/66 56/56
3 8G VM 3 2 4 --- --- --- 3 ( c oo l / h e a t ) 66/66 56/56
3 8G VM 4 3 0 --- --- --- 3 ( c oo l / h e a t ) 66/66 56/56
3 8G VM 4 3 6 --- --- --- 3 ( c oo l / h e a t ) 69/69 59/59
3 8G VM 5 4 2 --- --- --- 3 ( c oo l / h e a t ) 68/68 58/58
Indoor Units
Model Number
Low Medium High Turbo
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
4 0G VM 0 0 9 --- --- --- 3 36.0 26.0 45.0 35.0 47.0 37.0 51.0 41.0
4 0G VM 0 1 2 --- --- --- 3 38.0 28.0 46.0 36.0 48.0 38.0 52.0 42.0
4 0G VM 0 1 8 --- --- --- 3 45.0 35.0 50.0 40.0 54.0 44.0 56.0 46.0
NOTES:
1. Sound power ratings are per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.