EasyManua.ls Logo

Carrier 48HC*04–14 - Puron (R-410 A) Refrigerant; Refrigerant Charge

Carrier 48HC*04–14
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16
DFT 2
DFT1
FILTER
DRIER
FILTER
DRIER
1A
2A
OUTDOOR COIL
INDOOR COIL
ACCUMULATOR
ACCUMULATOR
HPS1
STRAINER
HEATING LIQUID LINES
STRAINER
1C
2C
2D
1D
TXV 2
TXV1
COOLING LIQUID LINES
LPS/LOC
2B
1B
HPS2
COMPRESSOR
COMPRESSOR
COMP 2
COMP 1
ACCUTROL
C12046
Fig. 20 -- Typical TXV Piping Schematic
Refrigerant System Pressure Access Ports
There are two access ports in the system -- on the suction
tube near the c ompressor and on t he discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
male flare couplings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring--closed check valve core screwed into the base. See
Fig. 21. This check valve is permanently assembled into
this core body and cannot be serviced separately; replace
the e ntire core body if necessary. Service tools are
available from RCD that allow the replacement of the
chec k valve core without having to re cover the entire
system refrigerant charge. Apply compressor refrigerant
oil to the check valve core’s bottom o--ring. Install the
fitting body with 96 10 in--lbs (10.85 1.1 Nm) of
torque; do not overtighten.
PURONR (R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system. Puron (R--410A) refrigerant is provided in pink
(rose) colored cylinders.
Puron (R--410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders are availa ble with and
without dip tubes; cylinders with dip tubes will have a
labe l indicat ing this feature. For a cyl inder with a dip
tube, place the cylinder in the upright position (access
valve at the top) when removing liquid refrigerant for
charging. For a cyl inder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly recommended that refri gerant a lways be removed
from the cylinder as a liquid. Admit liquid refri gerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
devic e at the gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder as a
vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on the units
nameplate. Refer to Carrier GTAC2--5 Charging,
Recovery, Recycling and Reclamation training manual
and the following procedures.
Unit panels must be in pla ce when unit is operati ng during
the charging procedure.
48HC

Table of Contents

Related product manuals