5
EVALUATING MOTOR SPEED
The direct drive ECM blower motor uses a constant speed design. 
Motor speed is controlled by a 0-10 vdc signal, where 10 vdc is 
equal to motor’s maximum rpm. 
SELECTING FAN SPEED
All units come factory set for 7.8 vdc or approximately 78% of the 
motor’s maximum speed. Fan speed should be set per job specifi-
cation cfm (cubic feet per minute) and ESP (external static pres-
sure) required and per Fan speed set up label included on the unit’s 
high voltage cover. In some cases, the Fan Speed Set Up label may 
already include the field setting if unit was previously installed. 
Check the box on the lower half of the label to see if the field volt-
age setting was filled in and if so, set fan speed to that voltage. 
Otherwise see detailed instructions below.
NOTE: Fan Speed Set-Up is for full load airflow. If the unit has 
multiple stages of cooling, low cool and ventilation may operate at 
lower fan rpms. This offset is factory set and controlled by the 
UCB. If fan speed verification is being done with a strobe, fan 
speed should be verified in all unit operation modes.
Units with Electro-mechanical controls
The Fan Speed set up controls are located on the lower section of 
the Unit Control Board (UCB). See Fig. 7 for location.
1. Check the job specifications for the cfm (cubic feet per 
minute) and ESP (external static pressure) required.
2. Using the chart on the Fan Speed Set Up labels (see Fig. 8), 
calculate the vdc from the cfm and ESP for the base.
3. If installing any accessories listed at the bottom of the Set 
Up Label, add accessory vdc to base unit vdc in upper por-
tion of label.
NOTE: The Fan Speed Set Up labels are located on the High 
Voltage cover in the Control Box.
4. Connect a multimeter to the vdc terminals on the UCB.
5. Set the Range Switch to either A, B, or C per the Switch 
Range table.
6. Using a straight blade screwdriver turn the vdc control dial 
to fine tune the vdc reading.
7. Record the reading in the Field Setting field.
NOTE: Fan set-up vdc is not affected by the operating stage of 
the unit.
NOTE: For units equipped with the Humidi-MiZer option, when 
replacing the UCB cut JMP 1,2 and 3 in the REHEAT/HP section 
of the replacement UCB.
Fig. 7 — UCB Fan Speed Controls - 3-Phase Units
Fan Speed Set Up Controls