58TN0B/58TN1B: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
A02068
Fig. 43 – Horizontal Right Application-Vent Elbow Left
A03219
Fig. 44 – Horizontal Right Application - Vent Elbow Left then Up
Notes for Venting
1. For common vent, vent connector sizing and vent material: United
States use the NFPA 54/ANSI Z223.1.
2. Immediately increase to 5-in. (102 mm) or 6-in. (152 mm) vent
connector outside furnace casing when 5-in. (127 mm) vent
connector is required, refer to Note 1 above.
3. Side outlet vent for upflow and downflow installations must use
Type B vent immediately after exiting the furnace, except when
factory-approved Downflow Vent Guard Kit is used in the
downflow position. See Product Data Sheet for accessory listing.
4. Type-B vent where required, refer to Note 1 above.
5. A 4-in.(102 mm) single-wall (26 ga. min.) vent must be used inside
furnace casing and when the factory-approved Downflow Vent
Guard Kit is used external to the furnace. See Product Data Sheet
for accessory listing.
6. Accessory Downflow Vent Guard Kit required in downflow
installations with lower vent configuration. See Product Data Sheet
for accessory listing.
7. Chimney Adapter Kit may be required for exterior masonry
chimney applications. Refer to Chimney Adapter Kit for sizing and
complete application details. See Product Data Sheet for accessory
listing.
8. Secure vent connector to furnace elbow with (2) corrosion-resistant
sheet metal screws, spaced approximately 180° apart.
9. Secure all other single wall vent connector joints with (3) corrosion
resistant screws spaced approximately 120° apart. Secure Type-B
vent connectors per vent connector manufacturer’s
recommendations.
SEE NOTES: 1,2,4,5,7,8,9 on the page
following these figures
Table 13 – Air Delivery - CFM (with Filter)*
045C17--12
Available Cooling Airflow
Settings (CFM)
488 525 555 600 650 700 740
*
800 875 925 975 1000
†
1050
1138 1200 1225 1300 1400 1480 1600
Available Constant Fan
Airflow Settings (CFM)
‡
488 525 555 600 650 700 740 800 875 925 975 1000 1050
1138 1200 1225
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow ESP (in. w.c.)
1400 0.7
1480 0.5
1600 0.3
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 1695 1670 1640 1605 1565 1530 1490 1445 1400 1360
070C14--12
Available Cooling Airflow
Settings (CFM)
400 450 488 525 555 600 650 700 740
*
800 875 925 975
1000
†
1050 1138 1200 1225 1300 1400
Available Constant Fan
Airflow Settings (CFM)
‡
400 450 488 525 555 600 650 700 740 800 875 925 975
1000 1050 1138
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow ESP (in. w.c.)
1200 0.8
1225 0.8
1300 0.6
1400 0.4
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 1430 1430 1420 1390 1355 1315 1275 1235 1195 1155