58TN0B/58TN1B: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
070C17--16
Available Cooling Airflow
Settings (CFM)
488 525 555 600 650 700 740 800 875 925 975 1000
*
1050
1138 1200 1225 1300
1400 1480 1600
Available Constant Fan
Airflow Settings (CFM)
488 525 555 600 650 700 740 800 875 925 975 1000 1050
1138 1200 1225
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow Setting ESP (in. w.c.)
1480 0.9
1600 0.7
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 1655 1655 1655 1655 1650 1645 1615 1570 1520 1475
070C21--20
Available Cooling Airflow
Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225
*
1300
1400 1480 1600 1625
1750 1850 1911 2000
Available Constant Fan
Airflow Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225 1300
1400
1480 1600
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow ESP (in. w.c.)
1850 0.9
1911 0.8
2000 0.5
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 2095 2095 2100 2100 2070 2035 1995 1960 1920 1880
090C17--16
Available Cooling Airflow
Settings (CFM)
400 450 488 525 555 600 650 700 740 800 875 925 975
1000
*
1050 1138 1200 1225 1300
1400 1480 1600
Available Constant Fan
Airflow Settings (CFM)
400 450 488 525 555 600 650 700 740 800 875 925 975
1000 1050
1138
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow ESP (in. w.c.)
1300 0.9
1400 0.7
1480 0.5
1600 0.1
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 1595 1560 1525 1490 1455 1420 1385 1340 1280 1220
090C21--20
Available Cooling Airflow
Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225
*
1300
1400 1480 1600 1625
1750 1850 1911 2000 2100 2179 2200
Available Constant Fan
Airflow Settings (CFM)
650 700 740 800 875 925 975 1000 1050 1138 1200 1225 1300
1400
1480 1600
Airflow reduces by 2% -
3% per 0.1 of ESP above
the noted static for these
airflow settings
Airflow Setting ESP (in. w.c.)
2000 0.8
2100 0.7
2179 0.6
2200 0.5
Max Cooling ESP 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
**
Max Cooling CFM 2290 2290 2290 2285 2270 2230 2185 2130 2070 2015
Table 13 – Air Delivery - CFM (with Filter)* (Continued)