EasyManua.ls Logo

Carrier 59SC2A - Installation Procedures and Connections; Installation Steps

Carrier 59SC2A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59SC2A
INSTALLATION
This
furnace
is
certified
to
leak
2%
or
less
of
nominal
air
conditioning
CFM
delivered
when
pressurized
to
1-in.
water
column
with
all
present
air
inlets,
including
bottom
closure
in
upflow
and
horizontal
applications,
air
outlets,
and
plumbing
and
electrical
ports
sealed.
Upflow
Installation
NOTE:
The
furnace
must
be
pitched
as
shown
in
Fig.
24
for
proper
condensate
drainage.
Supply
Air
Connections
For
a
furnace
not
equipped
with
a
cooling
coil,
the
outlet
duct
shall
be
provided
with
a
removable
access
panel.
This
opening
shall
be
accessible
when
the
furnace
is
installed
and
shall
be
of
such
a
size
that
the
heat
exchanger
can
be
viewed
for
possible
openings
using
light
assistance
or
a
probe
can
be
inserted
for
sampling
the
air
stream.
The
cover
attachment
shall
prevent
leaks.
Connect
supply-air
duct
to
flanges
on
furnace
supply-air
outlet.
Bend
flange
upward
to
90°
with
wide
duct
pliers.
See
Fig.
21.
The
supply-air
duct
must
be
connected
to
ONLY
the
furnace
supply-outlet-air
duct
flanges
or
air
conditioning
coil
casing
(when
used).
DO
NOT
cut
main
furnace
casing
side
to
attach
supply
air
duct,
humidifier,
or
other
accessories.
All
supply
side
accessories
MUST
be
connected
to
duct
external
to
furnace
main
casing.
Return
Air
Connections
CUA
Le:
FIRE
HAZARD
A
failure
to
follow
this
warning
could
cause
personal
injury,
death
and/or
property
damage.
Never
connect
return-air
ducts
to
the
back
of
the
furnace.
Follow
instructions
below.
The
return-air
duct
must
be
connected
to
bottom,
sides
(left
or
right),
or
a
combination
of
bottom
and
side(s)
of
main
furnace
casing.
Bypass
humidifier
may
be
attached
into
unused
return
air
side
of
the
furnace
casing. See
Fig.
25, 26,
and
27.
Bottom
Return
Air
Inlet
These
furnaces
are
shipped
with
bottom
closure panel
installed
in
bottom
return-air
opening.
Remove
and
discard
this
panel
when
bottom
return
air
is
used.
To
remove
bottom
closure
panel,
perform
the
following:
1.
Tilt or
raise
furnace
and
remove
4
screws
holding
bottom
plate.
See
Fig.
23.
.
Remove
bottom
plate.
Ww
be
.
Remove
bottom
closure
panel.
fs
.
Reinstall
bottom
plate
and
screws.
Side
Return
Air
Inlet
These
furnaces
are
shipped
with
bottom
closure panel
installed
in
bottom
return-air
opening.
This
panel
MUST
be
in
place
when
only
side
return
air
is
used.
NOTE:
Side
return-air
openings
can
be
used
in
UPFLOW
and
some
HORIZONTAL
configurations.
Do
not
use
side
return-air
openings
in
DOWNFLOW
configuration.
See
Fig.
25, 26,
and
27.
Leveling
Legs
(If
Desired)
In
upflow
position
with
side
return
inlet(s),
leveling
legs
may
be
used.
See
Fig.
22.
Install
field-supplied,
5/16
x
1-1/2
in.
(8
x
38
mm)
(max)
corrosion-resistant
machine
bolts,
washers
and
nuts.
NOTE:
Bottom
closure
must
be
used
when
leveling
legs
are
used.
It
may
be
necessary
to
remove
and
reinstall
bottom
closure panel
to
install
leveling
legs.
To
remove
bottom
closure
panel,
see
Item
1
in
Bottom
Return
Air
Inlet
section
in
Step
1
above.
To
install
leveling
legs:
1.
Position
furnace
on
its
back.
Locate
and
drill
a
hole
in
each
bottom
corner
of
furnace.
bo
.
For
each
leg,
install
nut
on
bolt
and
then
install
bolt
with
nut
in
hole.
(Install
flat
washer
if
desired.)
3.
Install
another
nut
on
other
side
of
furnace
base.
(Install
flat
washer
if
desired.)
4.
Adjust
outside
nut
to
provide
desired
height,
and
tighten
in-
side
nut
to
secure
arrangement.
5.
Reinstall
bottom
closure panel
if
removed.
Downflow
Installation
NOTE:
The
furnace
must
be
pitched
as
shown
in
Fig.
24
for
proper
condensate
drainage.
Supply
Air
Connections
NOTE:
For
downflow
applications,
this
furnace
is
approved
for
use
on
combustible
flooring
when
any
one
of
the
following
3
accessories
are
used:
¢
Special
Base,
KGASB
*
Cased
Coil
Assembly
Part
No.
CNPV,
CNRV,
CAP,
or
CAR
¢
Coil
Box
Part
No.
KCAKC
1.
Determine
application
being
installed
from
Table
8.
2,
Construct
hole
in
floor
per
Table
8
and
Fig.
20.
3.
Construct
plenum
to
dimensions
specified
in
Table
8
and
Fig.
20.
4.
Install
special
base
coil
assembly
or
coil
box
as
shown
in
Fig.
20.
NOTE:
It
is
recommended
that
the
perforated
supply-air
duct
flanges
be
completely
removed
from
furnace
when
installing
the
furnace
on
a
factory-supplied
cased
coil
or
coil
box.
To
remove
the
supply-air
duct
flange,
use
wide
duct
pliers
or
hand
seamers
to
bend
flange
back
and
forth
until
it
breaks
off.
Be
careful
of
sharp
edges.
See
Fig.
21.
4&
CAUTION
CUT
HAZARD
Failure
to
follow
this
caution
may
result
in
personal
injury.
Sheet metal
parts
may
have
sharp
edges
or
burrs.
Use
care
and
wear
appropriate
protective
clothing,
safety
glasses
and
gloves
when
handling
parts,
and
servicing
furnaces.
Connect
supply-air
duct
to
supply-air
outlet
on
furnace.
Bend
flange
inward
past
90°
with
wide
duct
pliers
See
Fig.
21.
The
supply-air
duct
must
be
connected
to
ONLY
the
furnace
supply
outlet
or
air
conditioning
coil
casing
(when
used).
When
installed
on
combustible
material,
supply-air
duct
must
be
connected
to
ONLY
the
factory-approved
accessory
subbase,
or
a
factory-approved
air
conditioning
coil
casing.
DO
NOT
cut
main
furnace
casing
to
attach
supply
side
air
duct,
humidifier,
or
other
accessories.
All
supply
side
accessories
MUST
be
connected
to
duct
external
to
furnace
casing.

Other manuals for Carrier 59SC2A

Related product manuals