CL-11
Filter Status (in filter section)
With the fan operating at high speed, turn the adjustment screw counterclockwise until the flag drops
Turn the adjustment screw 1-1/2 turns clockwise and reset the flag
Exhaust Fan (if equipped)
The exhaust fan is rotating in the correct direction
The exhaust fan is operating without vibration or other issue
The barometric exhaust damper is open and moves freely
Force the exhaust fan to 100% operation and record the amp draw on the start up log
Cooling
Note: cooling & dehumidification can only be performed when the outdoor air temperature is above 55°F
Verify all condenser fans are rotating and rotation direction is correct
Verify all condenser fans are rotating without vibration or other issue
Verify the compressor(s) are operating and compressor rotation is correct
Verify the compressor(s) are operating without vibration or other issue. Note: size 03-018 units have a lead circuit
digital compressor that will unload/load during operation, leading to some vibration and noise
Verify the outdoor air temperature on the startup log, if above 55°F proceed with cooling startup
(62W only) verify entering water flow and entering water temperature above 55°F
With the compressor(s) operating, subcooling reheat operating (if equipped), and hot gas reheat (HGRH) operating
at 100%, record the following information in the startup log:
· Compressor amp draw (all compressor)
· Evaporator coil leaving air temperature (DXLAT)
· Unit supply air temperature (SAT)
· (62W only) entering condenser water temperature (EWT) and condenser water flow rate
With the compressor(s) operating, subcooling reheat operating (if equipped), and hot gas reheat (HGRH)
disabled
, record the following information in the startup log:
· Suction line temperature (all circuits)
· Suction line pressure (all circuits)
· Discharge line temperature (all circuits)
· Discharge line pressure (all circuits)
· Record the compressor oil level (where available)
Energy Recovery Wheel (if equipped)
The exhaust fan is rerating without vibration or other issue
The ECW bypass damper (if equipped) is closed when the ECW is rotating
Force the ECW to 100% operation and record the amp draw on the start up log
For units with ECW defrost, for the ECW to 10% speed and verify the wheel slows down
Gas Heat (if equipped)
Verify inducer fan operation
Verify spark and ignition
With the supply fan operation at 100% speed or the balanced speed and the gas heat operating at high fire (100%
capacity), record the following information in the startup log:
· Outdoor air temperature (OAT)
· Unit supply air temperature (SAT)
· Inlet pressure (all furnaces)
· Manifold pressure (all furnaces)
· Flue gas CO and CO
2
levels (all furnaces)
· Inducer draft fan pressure (all furnaces)