Carrier 62X Series - STARTUP CHECKOUT; Verify Test Mode has been disabled (HomeSetupTest) by changing Run Test to “Off”; Verify all manual overrides have been turned off, unless set by air balance (HomeSetupMisc. SettingsMan Ovrd); Verify all sensor offsets have been turned off, unless set by calibration (HomeSetup Calibration)

Carrier 62X Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CL-12
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
With the supply fan operation at 100% speed or the balanced speed and the gas heat operating at low fire (50%
capacity for 2 stage units, 25% capacity for 4 stage units, 20% capacity for 5:1 modulating units, and 10% capacity for
10:1 modulating units), record the following information in the startup log:
· Outdoor air temperature (OAT)
· Unit supply air temperature (SAT)
· Inlet pressure (single furnace)
· Manifold pressure (single furnace)
· Flue gas CO and CO
2
levels (single furnace)
· Inducer draft fan pressure (single furnace)
Electric Heat (if equipped)
With the supply fan operation at 100% speed or the balanced speed and the electric heater operating at 100%
capacity, record the following information in the startup log:
· Outdoor air temperature (OAT)
· Unit supply air temperature (SAT)
· Heater amp draw
With the supply fan operation at 100% speed or the balanced speed and the electric heater operating at 50%
capacity, record the following information in the startup log:
· Outdoor air temperature (OAT)
· Unit supply air temperature (SAT)
· Heater amp draw
Hot Water Heat (if equipped)
With the supply fan operation at 100% speed or the balanced speed and the electric heater operating at 50%
capacity, record the following information in the startup log:
· Outdoor air temperature (OAT)
· Unit supply air temperature (SAT)
· Heater amp draw
Field Installed Heat (if equipped)
With the supply fan operation at 100% speed or the balanced speed and the electric heater operating at 100%
capacity, record the following information in the startup log:
· Heater operation and signal response
With the supply fan operation at 100% speed or the balanced speed and the electric heater operating at 50%
capacity, record the following information in the startup log:
· Heater operation and signal response
STARTUP CHECKOUT
Verify Test Mode has been disabled (HomeSetupTest) by changing Run Test to “Off”
Verify all manual overrides have been turned off, unless set by air balance (HomeSetupMisc. SettingsMan
Ovrd)
Verify all sensor offsets have been turned off, unless set by calibration (Home
Setup Calibration)
Verify that the current time and date has been set in the controller (Home
SetupMisc. SettingsBAS Setup Set
Time and Date)
Verify emergency shutdown is set to “Off” (Home
SetupTech. Setup.)
Verify manual occupancy control is set to “Off” (Home
SetupTech. Setup.)
Verify configured occupancy control is set to the last known setting (HomeSetupTech. Setup.)
Set Enable Unit Operation to “On” (Home
SetupTech. Setup.)
Verify no alarms are displayed (Home
Alarms)
The unit should now restore normal operation