85
APPENDIX A — BAS COMMISSIONING (CONT)
6. Turn on the controller’s power.
7. To verify communication with the network, get a Module Sta-
tus report in the WebCTRL interface for a controller on the
ARCNET network.
NOTE: This step requires that you have set up the router in
SiteBuilder and downloaded it from the WebCTRL interface.
TO WIRE TO A BACNET MS/TP NETWORK
An MS/TP network can be wired to either Port S1 or Port S2.
1. Turn off the LS-1628u’s power.
2. Check the communication wiring for shorts and grounds.
3. Connect the communications wiring to the Port S1 or Port S2
screw terminals labeled Net+, Net-, and Shield.
NOTE: Use the same polarity throughout the network
segment.
4. If you are using Port S1, set the Port S1 Configuration to
switch to 1.
NOTE: If Port S1 is not being used for any network, set this
rotary switch to 0.
5. If the LS-1628u is at either end of a network segment, set the
port’s End of Net? switch to Yes.
NOTE: The controller’s End of Net switch applies network
termination and bias. If the controller is at the end of a net-
work segment that includes a DIAG485 that has its Bias
jumper in the ON position, set the End of Net? switch to
No and connect a 120 ohm termination resistor to the Net+
and Net- terminals. See DIAG485 Technical Instructions
for more information.
6. Turn on the controller’s power.
7. To verify communication with the network, get a Module Sta-
tus report in the WebCTRL interface for a controller on the
MS/TP network.
NOTE: This step requires that you have set up the router in
SiteBuilder and downloaded it from the WebCTRL interface.
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air
Display Name Read/Write
BACnet
Description
Reference Name Type ID
Alarm Reset R/W alarm_reset BV 900 Read/write point to Reset Alarms.
Alarm Status R alarm_status BV 851 The current Alarm Status of Unit.
Allow Compressor
Disable
R/W comp_dis BV 539
Read/write point that Allows Compressor Disable on Low Supply
Fan % or Low OAT.
Allow Zone Set Point
Adjust
R/W zat_sp_adj_en BV 202
This point will enable the Sone setpoint adjustment on the zone
sensor (Default is plus or minus 5°F).
Aux. Htg. Enable R ahtg_en BV 580 The current Auxillary Heating Enable Status.
BAS Com Lost OAT/
OARH Status
R bas_com_lost_on BV 1102
BAS communication lost code. This point displays the status of
the lost of communication for the OAT/OARH option.
BAS Comm. Lost Delay R/W
bas_comm_lost_d
elay
AV 103
BAS commuication lost code. Delay on Make timer (Default 60
seconds). The input must change state within time period.
BAS Communication
Lost
R bas_comm_lost BV 107
BAS communication lost code. This point displays the status of
the lost of communication for the schedule option.
BAS LOST R
bas_comm_lost_al
arm
BV 899
The current BAS Lost Alarm for Schedule Option.
BAS Manual Occ Control R/W occ_en BV 101
Read/write point will place the unit into unoccupied/occupied
mode with Occupancy Control Option is set to BAS Control.
C1 ALARM R c1_alarm BV 863 The current Compressor #1 Alarm Status.
C1 Command R c1_cmd BV 243 Compressor #1 Start Command (BO-2).
C1 Freeze Status R c1_freeze_stat BV 555 The current Compressor #1 Freeze Status.
C1 HAND R c1_hand_alarm BV 873 The current Compressor #1 Hand Alarm Status.
C1 STOP R c1_stop_alarm BV 864 The current Compressor #1 Stop Alarm Status.
C1/C2 Stop Disables Unit R/W
c1c2_stop_disable
s_unit
BV 847
Read/write to Enable the Unit to shutdown if compressors in Stop
Alarm.
C1DIG Percentage
Before C2 SP
R/W dig1_pct_c2_sp AV 6402
Read/write point for Compressor #1 demand for Compressor #2
Start (Default is 95%).
C2 ALARM R c2_alarm BV 877 The current Compressor #2 Alarm Status.
C2 Command R c2_cmd BV 244 Compressor #1 Start Command (BO-3).
C2 Freeze Status R c2_freeze_stat BV 556 The current Compressor #2 Freeze Status.
C2 HAND R c2_hand_alarm BV 887 The current Compressor #2 Hand Alarm Status.
C2 STOP R c2_stop_alarm BV 878 The current Compressor #2 Stop Alarm Status.
CFI ALARM R cfi_alarm BV 893 The current Clogged Filter Indicator Alarm Status.
CFI Status R cfi_stat BV 232 Clogged Filter Indicator Switch Status (N.O.).
Clg #1 Enable SP R/W clg1_en_sp AV 307 The setpoint for Cooling #1 Enable (Default varies).
Clg #2 Enable SP R/W clg2_en_sp AV 327 The setpoint for Cooling #1 Enable. (Default varies).
Clg Modulation SP Occ R/W clg_mod_sp_o AV 375 The setpoint for Occupied Cooling Modulation. (Default is 55°F).
Clg SAT SP Occ R/W clg_sat_sp_o AV 313
The setpoint for Occupied Cooling Supply Air Temperature
(Default varies).
Clg SAT SP Unocc R/W clg_sat_sp_u AV 314
The setpoint for Unoccupied Cooling Supply Air Temperature
(Default varies).
CO2 Dead Band R/W co2_db AV 217 The CO
2
Upper Deadband for High CO
2
Alarm (Default 200 ppm)
CO2 FAIL R co2_failure BV 854 The current CO
2
Sensor Alarm status.
CO2 From BAS R/W co2_bas AV 213
The current Carbon Dioxide reading (CO
2
) written to the
controller by the BAS system.
CO2 Occupancy Status R co2_occ_stat BV 203
This point will dislplay the status for the CO
2
enable for schedule
control for the CO
2
option.
CO2 Set Point #1 R/W co2_sp1 AV 215 The CO
2
setpoint for Occupancy Control. (Default 300ppm).
CO2 Set Point #2 R/W co2_sp2 AV 216 The CO
2
setpoint for High CO
2
Alarm (Default 1200ppm).