9
Fig. 2 — Equipment Touch 2™ Connection to Unit Controller
Controller Ports
The OptiCORE controller has sixteen universal outputs (UO) and
twenty-eight universal inputs (UI). All of the input and output (I/
O) settings are preconfigured from the factory to reflect the facto-
ry unit configuration.A predetermined amount of the controller’s
I/O are field configurable to the factory configurations. See Fig. 3
for typical controller layout.
UNIVERSAL INPUTS
All universal inputs can be set to read voltage, amperage, resis-
tance (temperature), and discrete contact. All inputs are config-
ured via software (Factory Program.) See Table 4 and 5 for typical
universal inputs.
NOTE: The universal inputs and analog outputs are
preconfigured at the factory for each factory option package
for the 62X series. Inputs UI-2, UI-4, UI-10, and UI-11 are set
to read 0 to 10 V. All other UIs are set to read resistance
(temperature) and dry contacts. Outputs UO-01, UO-02, UO-
04, UO-05, and UO-06 are set to output voltage. Outputs U-7
(Compressor modulation via Unloader (Digital compressor, 3-
18 tons) or VFD (Variable Speed compressor, 20-55 tons). See
Tables 4 and 5 for default controller configuration.
Table 4 — Inputs
NUMBER NAME SENSOR TYPE DESCRIPTION
OptiCORE LS-1628u CONTROLLER — UNIVERSAL INPUTS WITH ERV
UI-01 ECA-T Thermistor Entering Coil Air Temperature
UI-02 ECA-RH 0-10 vdc Entering Coil Relative Humidity
UI-03 SAT Thermistor Supply Air Temperature
UI-04 SA-RH 0-10 vdc Supply Air Relative Humidity
UI-05 OAT Thermistor Outside Air Temperature
UI-06 RAT Thermistor Return Air Temperature
UI-07 WExAT Thermistor Wheel Exhaust Air Temperature
UI-08 DxLAT1 Thermistor DX Coil Leaving Air Temperature 1
UI-09 DxLAT2 Thermistor DX Coil Leaving Air Temperature 2
UI-10 SF-DPT or AMS 0-10 vdc Supply Fan Duct Pressure Transducer or Airflow Monitoring Station
UI-11 ZN-DPT or AMS 0-10 vdc
Zone (Building)/Exhaust Pressure Transducer or Airflow Monito
ring
Station
UI-12 S/S contact Normally Open Contact
Start/Stop Contact, (By Others) Occupancy Control must be set to
S/S SWITCH” in the controls screen of the Equipment Touch
UI-13 OADA-A Normally Open Contact Two Position Outdoor Air Damper
UI-14 WM-CS Normally Open Contact Wheel Motor Current Sensor
UI-15 EF-CS Normally Open Contact Exhaust Fan Current Sensor
UI-16 SF-CS Normally Open Contact Supply Fan Current Sensor
UI-17 CC1-CS Normally Open Contact Cooling Circuit 1 Current Sensor
UI-18 LPS1 Normally Open Contact Low Pressure Switch Cooling Circuit 1
UI-19 HPS1 Normally Open Contact High Pressure Switch Cooling Circuit 1
UI-20 CC2-CS Normally Open Contact Cooling Circuit 2 Current Senosr
UI-21 LPS2 Normally Open Contact Low Pressure Switch Cooling Circuit 2
UI-22 HPS2 Normally Open Contact High Pressure Switch Cooling Circuit 2
UI-23
UI-24
UI-25 CFI Normally Open Contact Clogged Filter Indicator