PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
vent connector capacity is equal to or lower than the low fire rate of
the furnace and the FAN-Max vent connector capacity is equal to or
higher than the furnace high fire rate.
3. Do not vent this Category I furnace into a single wall dedicated or
common vent. The dedicated or common vent is considered to be
the vertical portion of the vent system that terminates outdoors.
4. Vent connectors serving Category I furnaces shall not be connected
into  any  portion  of  a  mechanical  draft  system  operating  under
positive pressure.
5. Do not vent this appliance with any solid fuel burning appliance. 
6. Category I furnaces must  be vented vertically or nearly  vertically
unless equipped with a  listed mechanical venter. See SIDEWALL
VENTING section.
7. Do not vent this appliance into an unlined masonry chimney. (Refer
to Chimney Inspection Chart, Fig. 37).
A10133
Fig. 37 – Chimney Inspection Chart 
Masonry Chimney Requirement
NOTE:  These  furnaces  are  CSA  design-certified  for  use  in  exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit number marked on the furnace rating plate. 
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances ANSI/NFPA 211 in the United States and must
be in good condition. 
U.S.A.-Refer  to  Sections  13.1.8  and  13.2.20  of  the  NFPA  54/ANSI
Z223.1 or the authority having jurisdiction to determine whether relining
is required. If relining is required, use a properly sized listed metal liner,
Type-B vent, or a listed alternative venting design.
NOTE:  See  the  NFPA  54/ANSI  Z223.1  13.1.9  and  13.2.20  regarding
alternative  venting  design and  the exception, which  cover installations
such  as  our  Chimney Adapter  Kits  which are  listed for  use  with these
furnaces.   See Product Data Sheet for accessory listing.
The Chimney Adapter Kit is a listed alternative venting system for these
furnaces. See the kit instructions for complete details. 
This  furnace  is  permitted  to  be  vented  into  a  clay  tile-lined  masonry
chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hood equipped
appliance, and
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected
to the venting system being placed into operation could result in carbon
monoxide poisoning or death. 
The following steps shall be followed for each appliance connected to
the  venting  system  being  placed  into  operation,  while  all  other
appliances connected to the venting system are not in operation:
1. Seal any unused openings in venting system.
2. Inspect the venting system for proper size and horizontal pitch,
as  required  in  the  National  Fuel  Gas  Code,  NFPA  54/ANSI
Z223.1  and  these  instructions.  Determine  that  there  is  no
blockage  or  restriction,  leakage,  corrosion  and  other
deficiencies, which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and  bathroom  exhausts,  so  they  are  operating  at  maximum
speed. Do not operate a summer exhaust fan.
6. Follow  the  lighting  instructions.  Place  the  appliance  being
inspected into operation. Adjust the  thermostat so appliance is
operating continuously.
7. Test  for  spillage  from  draft  hood  equipped  appliances  at  the
draft  hood  relief  opening  after  5  minutes  of  main  burner
operation. Use the flame of a match or candle.
8. If improper  venting is observed during any of the  above tests,
the  venting  system  must  be  corrected  in  accordance  with  the
National Fuel Gas Code, NFPA 54/ANSI Z223.1.
9. After it has been determined that  each appliance connected to
the  venting  system  properly  vents  when  tested  as  outlined
above, return doors, windows, exhaust fans, fireplace dampers
and  any  other  gas-fired  burning  appliance  to  their  previous
conditions of use.
CHIMNEY INSPECTION CHART
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances 
Consult
Par t C of
chimney adapter venting
instructions for
application
suitability
Is chimney
lined with properly
sized, listed liner or
Type-B vent?
Is chimney
to be dedicated to
a single
furnace?
Chimney
exposed to
outdoors below
roof line?
Repair
liner or top seal
or reline chimney as
necessary.
Mortar
or tile
debris?
Clay
tile misalignment,
missing sections,
gaps?
Debris
in cleanout?
Mortar, tile, metal vent,
fuel oil residue?
Is
liner and top
seal in good
condition?
Is chimney
property lined with
clay tile liner?
Crown
condition:
Missing mortar
or brick?
Rebuild
crown.
Ye s
Ye s
No
No
No
Reline
Ye s
Repair
Ye s
Ye s
Ye s
No
No
Remove mortar
and tile debris
Remove metal vent
or liner.
No
No
No
No
Ye s
Ye s
Suitable
Suitable
Not Suitable
Line chimney with property
sized, listed flexible metal
liner or Type-B vent per
NFGC 
 Vent
Sizing Tables and liner or
vent manufacturer’s
Installation instructions.
Install chimney
adapter per
instructions.
Chimney is
acceptable for use.
Install chimney
adapter per
instructions.
Consult
Par t B of
chimney adapter venting
instructions for
application
suitability.
Ye s
Not Suitable
Condensate
drainage at bottom
of chimney?
Ye s
No