PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
l. Proceed to Step 6, “Set Blower Off Delay” before installing 
blower access door. 
7. Set Blower Off Delay. (See Table 10.)
a. Remove blower access door if installed.
b. Turn Dip switch SW-7 or SW-8 ON or OFF for desired blower 
off delay. (See Fig. 36, Fig. 54 and Fig. 59).
 
8. Set thermostat heat anticipator.
a. Mechanical thermostat. Set thermostat heat anticipator to match 
the amp. draw of the electrical components in the R-W/W1 
circuit. Accurate amp. draw readings can be obtained at the wires 
normally connected to thermostat subbase terminals, R and W. 
The thermostat anticipator should NOT be in the circuit while 
measuring current.
(1.) Set SW1-2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter across the R and W subbase 
terminals or R and W wires at wall. (See Fig. 52.
A96316
Fig. 52 – Amp. Draw Check with Ammeter
(4.) Record amp. draw across terminals when furnace is in low 
heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat 
instructions and install on subbase or wall.
(6.)  Turn SW1-2 switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
9. Set Airflow  for  Air  Conditioning  -Single  Stage  and  High  Stage
Cooling. 
The ECM blower  can be  adjusted  for a  range  of  airflow for  Low
Speed  or  High  Speed  cooling.  See  Table 4-Air  Delivery  -  CFM
(With Filter). 
The cooling airflow is adjusted by turning Setup switches SW2-6,
SW2-7 and SW2-8 either ON or OFF. Select the required airflow.
(See Fig. 55).
NOTE: 5.5 ton airflow will truncate at 2200 cfm on applicable models.
For a complete explanation of cooling airflow, refer to the section titled
“Sequence of Operation.”
10. The  Continuous Fan airflow  selection via Setup  switches SW2-3,
SW2-4,  SW2-5  is  also  the  switch  setting  for  low-speed  cooling
when  the  furnace  is used  with a  two-speed cooling or heat  pump
unit. Refer to the Adjustments section (also Fig. 54 and Fig. 55) for
setup  switch  configurations. This  setup feature  allows continuous
fan airflow or low-cooling airflow to be adjusted.
The continuous fan speed can be further adjusted at the thermostat
using  the  Continuous  Blower  Speed  Selection  from  Thermostat
function.  Changing  the  continuous  fan  speed  at  the  thermostat
DOES NOT change the low speed cooling airflow selected at the
control  board.  See  the  section  titled  Continuous  Blower  Speed
Selection from Thermostat in the Sequence of Operation section of
this document.
 
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life. 
Recheck  temperature  rise.  It  must  be  within  limits  specified  on  the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above. 
Table 10 – Blower Off Delay Setup Switch
DESIRED HEATING MODE
BLOWER OFF DELAY (SEC.) 
SETUP SWITCH
(SW-7 AND -8)
POSITION 
SW1-7  SW1-8 
90  OFF  OFF 
120  ON  OFF 
150  OFF  ON 
180  ON  ON 
R Y W G
10 TURNS
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
 =  
0.5 AMPS FOR THERMOSTAT
     ANTICIPATOR SETTING
FROM UNIT 24-V
CONTROL TERMINALS
Table 11 – Gas Rate (CU ft./hr)
SECONDS G
FOR 1 
REVOLUTION 
SIZE OF TEST DIAL 
SECONDS 
FOR 1 
REVOLUTION 
SIZE OF TEST DIAL 
1 Cu 
Ft. 
2 Cu 
Ft. 
5 Cu 
Ft. 
1 Cu 
Ft. 
2 Cu 
Ft. 
5 Cu 
Ft. 
10  360  720  1800  50  72  144  360 
11  327  655  1636  51  71  141  355 
12  300  600  1500  52  69  138  346 
13  277  555  1385  53  68  136  340 
14  257  514  1286  54  67  133  333 
15  240  480  1200  55  65  131  327 
16  225  450  1125  56  64  129  321 
17  212  424  1059  57  63  126  316 
18  200  400  1000  58  62  124  310 
19  189  379  947  59  61  122  305 
20  180  360  900  60  60  120  300 
21  171  343  857  62  58  116  290 
22  164  327  818  64  56  112  281 
23  157  313  783  66  54  109  273 
24  150  300  750  68  53  106  265 
25  144  288  720  70  51  103  257 
26  138  277  692  72  50  100  250 
27  133  267  667  74  48  97  243 
28  129  257  643  76  47  95  237 
29  124  248  621  78  46  92  231 
30  120  240  600  80  45  90  225 
31  116  232  581  82  44  88  220 
32  113  225  563  84  43  86  214 
33  109  218  545  86  42  84  209 
34  106  212  529  88  41  82  205 
35  103  206  514  90  40  80  200 
36  100  200  500  92  39  78  196 
37  97  195  486  94  38  76  192 
38  95  189  474  96  38  75  188 
39  92  185  462  98  37  74  184 
40  90  180  450  100  36  72  180 
41  88  176  439  102  35  71  178 
42  86  172  429  104  35  69  173 
43  84  167  419  106  34  68  170 
44  82  164  409  108  33  67  167 
45  80  160  400  110  33  65  164 
46  78  157  391  112  32  64  161 
47  76  153  383  116  31  62  155 
48  75  150  375  120  30  60  150 
49  73  147  367