PG80VTLA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
circuits  switch  the  outdoor  unit  to  high-cooling  speed,  and  the
R-to-G-and-Y1-and-Y/Y2  circuits  transition  the  furnace  blower  motor
BLWM  to  high-cooling  airflow.  High-cooling  airflow  is  based  on  the
A/C selection. (See Fig. 55).
NOTE:  When  transitioning  from  low-cooling  to  high-cooling  the
outdoor unit compressor will shut down for 1 minute while the furnace
blower motor BLWM transitions to run at high-cooling airflow. 
The  electronic  air  cleaner  terminal  EAC-1  is  energized  with  115  vac
whenever the blower motor BLWM is operating. 
When the  thermostat is satisfied,  the  R-to-G-and-Y circuit  are  opened.
The outdoor unit stops, and the furnace blower BLWM and electronic air
cleaner  terminal  EAC-1  will  remain  energized  for  an  additional  90
seconds.  Jumper  Y1  to  DHUM  to  reduce  the  cooling  off-delay  to  5
seconds. (See Fig. 36).
c. Two-Stage Thermostat and Two-Speed Cooling 
See Fig. 34 for thermostat connections 
NOTE:  The  air  conditioning  relay  disable  jumper  ACRDJ  must  be
disconnected  to  allow  thermostat  control  of  the  outdoor  unit  staging.
(See Fig. 36).
The  thermostat  closes  the  R-to-G-and-Y1  circuits  for  low-cooling  or
closes  the  R-to-G-and-Y1-and-Y2  circuits  for  high-cooling.  The
R-to-Y1  circuit  starts  the  outdoor  unit  on  low-cooling  speed,  and  the
R-to-G-and-Y1  circuit  starts  the  furnace  blower  motor  BLWM  at
low-cooling  airflow  which  is  the  true  on-board  CF  selection.  (See
Table 4 and Fig. 55). The R-to-Y1-and-Y2 circuits start the outdoor unit
on  high-cooling  speed,  and  the  R-to-  G-and-Y/Y2  circuits  start  the
furnace  blower  motor  BLWM  at  high-cooling  airflow.  High-cooling
airflow is based on the A/C (air conditioning) selection. (See Fig. 55). 
The  electronic  air  cleaner  terminal  EAC-1  is  energized  with  115  vac
whenever the blower motor BLWM is operating. 
When  the  thermostat  is  satisfied,  the  R-to-G-and-Y1  or  R-to-
G-and-Y1-and-Y2 circuits are opened. The outdoor unit  stops, and the
furnace blower BLWM and electronic air cleaner terminal EAC-1 will
remain energized for an additional 90 seconds. Jumper Y1 to DHUM to
reduce the cooling off-delay to 5 seconds. (See Fig. 36).
4. Thermidistat Mode 
See Fig. 28, Fig. 29, and Fig. 30 for thermostat connections. 
The dehumidification output, DHUM on the Thermidistat should be
connected to the furnace control thermostat terminal DHUM. When
there is a dehumidify demand, the DHUM input is activated, which
means 24 vac signal is removed from the DHUM input terminal. In
other words, the DHUM input logic is reversed. The DHUM input
is turned ON when no  dehumidify demand exists. Once 24 vac is
detected  by  the  furnace  control  on  the  DHUM  input,  the  furnace
control operates in Thermidistat mode. If the DHUM input is low
for  more  than  48  hours,  the  furnace  control  reverts  back  to
non-Thermidistat mode. 
The  cooling  operation  described  in  item  3.  above  also  applies  to
operation with a Thermidistat. The exceptions are listed below:
a. Low cooling-When the R-to-G-and-Y1 circuit is closed and 
there is a demand for dehumidification, the furnace blower motor 
BLWM will drop the blower airflow to 90 percent of low-cooling 
airflow which is the true on-board CF selection. (See Table 4 and 
Fig. 55).
b. High cooling-When the R-to-G-and Y/Y2 circuit is closed and 
there is a demand for dehumidification, the furnace blower motor 
BLWM will drop the blower airflow to 90 percent of 
high-cooling airflow. High-cooling airflow is based on the A/C 
(air conditioning) selection. (See Fig. 55).
c. Cooling off-delay-When the “call for cooling” is satisfied and 
there is a demand for dehumidification, the cooling blower-off 
delay is decreased from 90 seconds to 5 seconds.
5. Continuous Blower Mode 
When  the  R-to-G  circuit  is  closed  by  the  thermostat,  the  blower
motor  BLWM  will  operate  at  continuous  blower  airflow.
Continuous  blower  airflow  selection  is  initially  based  on  the  CF
selection shown in Table 4 and Fig. 55. Factory default is shown in
Table 4. Terminal EAC-1 is energized as long as the blower motor
BLWM is energized.During a call for heat, the furnace control CPU
will  transition  the  blower  motor  BLWM  to  continuous  blower
airflow or low-heat airflow whichever is lowest. The blower motor
BLWM will remain ON until the main burners ignite then shut OFF
and remain OFF for the blower-ON delay (45 seconds in low-heat,
and 25 seconds in high-heat), allowing the furnace heat exchangers
to heat up more quickly, then restarts at the end of the blower-ON
delay period at low-heat or high-heat airflow, respectively. 
The blower motor BLWM will revert to continuous-blower airflow
after  the  heating  cycle  is  completed.  In  high-heat,  the  furnace
control CPU will drop the blower motor BLWM to low-heat airflow
during the selected blower-OFF delay period before transitioning to
continuous-blower airflow. 
When  the  thermostat  “calls  for  low-cooling”,  the  blower  motor
BLWM  will  switch  to  operate  at  low-cooling  airflow.  When  the
thermostat  is  satisfied,  the  blower  motor  BLWM  will  operate  an
additional  90  seconds  at  low-cooling  airflow  before  transitioning
back to continuous-blower airflow. 
When  the  thermostat  “calls  for  high-cooling”,  the  blower  motor
BLWM will operate at high cooling airflow. When the thermostat is
satisfied,  the  blower  motor  BLWM  will  operate  an  additional  90
seconds  at  high-cooling  airflow  before  transitioning  back  to
continuous-blower airflow. When the R-to-G circuit is opened, the
blower  motor  BLWM  will  continue operating  for  an  additional 5
seconds,  if  no  other  function  requires  blower  motor  BLWM
operation. 
Continuous Blower Speed Selection from Thermostat 
To select different continuous-blower airflow from the room thermostat,
momentarily  turn  off  the  FAN  switch  or  push  button  on  the  room
thermostat for 1-3 seconds after the blower motor BLWM is operating.
The furnace control CPU will shift the continuous-blower airflow from
the factory setting to the next highest CF selection airflow. (See Table 4
and  Fig. 55).  Momentarily  turning  off  the  FAN  switch  again  at  the
thermostat  will  shift  the  continuous-blower  airflow  up  one  more
increment. If you repeat this procedure enough you will eventually shift
the continuous-blower airflow to the lowest CF selection. (See Table 4
and Fig. 55). The selection can be changed as many times as desired and
is  stored  in  the  memory  to  be  automatically  used  following  a  power
interruption.
NOTE:  If  the  blower-off  delay  is  set  to  the  maximum,  the  adjustable
continuous-fan feature is locked (i.e., fan speed cannot be changed from
its current setting).
6. Heat pump
See Fig. 30 - Fig. 33 for thermostat connections. 
When installed with a heat pump, the furnace control automatically
changes the timing sequence to avoid long blower off times during
demand  defrost  cycles.  Whenever W/W1  is  energized  along  with
Y1 or Y/Y2, the furnace control CPU will transition to or bring on
the  blower  motor  BLWM  at  cooling  airflow  or  low-heat  airflow,
whichever is lowest. The blower motor BLWM will remain on until
the  main  burners  ignite  then  shut  OFF  and  remain  OFF  for  25
seconds before coming back on at heating airflow. When the W/W1
input signal disappears, the furnace control begins a normal inducer
post-purge period while changing the blower airflow. If Y/Y2 input
is still energized the furnace control CPU will transition the blower
motor  BLWM  airflow  to  cooling  airflow.  If  Y/Y2  input  signal
disappears  and  the Y1  input  is  still  energized  the  furnace  control
CPU  will  transition  the  blower  motor  BLWM  to  low-cooling
airflow. If both the Y1 and Y/Y2 signals disappear at the same time,
the blower motor BLWM will remain on at low-heat airflow for the
selected blower-OFF delay period. At the end of the blower- OFF