EasyManua.ls Logo

Carrier AquaForce 30XW-V - 9 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA; 9.1 Compressors; 9.2 Oil filter; 9.3 Refrigerant

Carrier AquaForce 30XW-V
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA
9.1 - Compressors
30XW-V/30XWHV units use 06T geared twin-screw
compressors equipped with a variable capacity slide valve
and controlled by a speed variator.
Compressor capacity control is ensured by successive use of
speed variation (using a frequency variator) and swept volume
variation at the screws (using the slide valve).
The combination of these two control modes permits ne 
control of the unit capacity between 20% and 100%.
• The 06T compressor models used are:
06TUX483, 06TUX554, 06TVX680, 06TVX753
9.2 - Oil lter
The 06T screw compressor has an independent oil lter.
9.3 - Refrigerant
30XW-V/30XWHV units only use refrigerant R-134a.
9.4 - Lubricant
The 06T screw compressor is approved for use with lubricants:
Carrier specication PP47-32
Carrier specication PP47-13
9.5 - Oil supply solenoid valve
An oil supply solenoid valve is installed on the oil return line as
standard to isolate the compressor from oil flow when the
compressor is not operating. The oil solenoid valve is field
replaceable.
9.6 - Pressure vessels
9.6.1 - General
Monitoring  during  operation,  re-qualication,  re-testing  and  re-
testing dispensation:
Follow the regulations on monitoring pressurised equipment.
It is normally required that the user or operator sets up and
maintains a monitoring and maintenance le.
If no regulations exist or to complement regulations, follow
the control programmes of EN 378.
If they exist follow local professional recommendations.
Regularly inspect the condition of the coating (paint) to
detect blistering resulting from corrosion. To do this, check
a non-insulated section of the container or the rust formation
at the insulation joints.
Regularly check for possible presence of impurities (e.g.
silica grains) in the heat exchange uids. These maybe the 
cause of the wear or corrosion by puncture.
Filter the heat exchange uid check and carry out internal 
inspections as described in EN 378, annexe C.
In case of re-testing please refer to the maximum operating
pressure given on the unit nameplate.
The reports of periodical checks by the user or operator must
be included in the supervision and maintenance le.
9.6.2 - Repair
Any  repair  or  modication,  including  the  replacement  of  moving 
parts:
must  follow  local  regulations  and  be  made  by  qualied 
operators  and  in  accordance  with  qualied  procedures, 
including changing the heat exchanger tubes.
must be made in accordance with the instructions of the
original manufacturer. Repair and modification that
necessitate permanent assembly (soldering, welding,
expanding etc.) must be made using the correct proce-dures
and by qualied operators.
An indication of any modication or repair must be shown 
in the monitoring and maintenance le.
9.6.3 - Recycling
The unit is wholly or partly recyclable. After use it contains
refrigerant vapours and oil residue. It is coated by paint.
9.6.4 - Operating life
The evaporator and oil separator are designed for:
prolonged storage of 15 years under nitrogen charge with
a temperature difference of 20 K per day.
452000 cycles (start-ups) with a maximum difference of 6
K between two neighbouring points in the vessel, based on
6 start-ups per hour over 15 years at a usage rate of 57%.
9.6.5 - Corrosion allowances:
Gas side: 0 mm
Heat exchange uid side: 1 mm for tubular plates in lightly alloyed 
steels, 0 mm for stainless steel plates or plates with copper-nickel
or stainless steel protection.
9.6.6 - Evaporator
30XW-V/30XWHV  units  use  a  ooded  multi-tube  evaporator. The 
water circulates in the tubes and the refrigerant is on the outside
in the shell. The tubes are 3/4” diameter copper with an enhanced
surface inside and out. There is just  one  water  circuit with two 
water passes (one pass with option 100C, please refer to chapter
6.6 “Number of passes”).
The evaporator shell has a polyurethane foam thermal insulation
and a water drain and purge.
It has been tested and stamped in accordance with the applicable
pressure codes. The maximum standard relative operating pressure
is 2100 kPa for the refrigerant-side and 1000 kPa for the water-side.
These pressures can be different depending on the code applied.
The water connection of the heat exchanger is a Victaulic
connection.
The products that may be added for thermal insulation of the
containers during the water piping connection procedure must be
chemically neutral in relation to the materials and coatings to which
they are applied. This is also the case for the products originally
supplied by Carrier.
9.6.7 - Condenser and oil separator
30XW-V/30XWHV units use a heat exchanger that is a combination
condenser and oil separator. It is mounted below the evaporator.
Discharge  gas  leaves  the  compressor  and  ows  through  an 
external mufer to the oil separator, which is the upper portion of 
the heat exchanger. It enters the top of the separator where oil is
removed, andthenowsto the bottom portion of the vessel, where 
gas is condensed and subcooled. The tubes are 3/4” or 1” diameter
internally and externally nned copper tubes. 
There is just one water circuit with two water passes (one pass 
with option 102C, please refer to chapter 6.6 “Number of passes”).
For the heat pumps the condenser shell can have a polyurethane
foam thermal insulation (option 86) and a water drain and purge.
It has been tested and stamped in accordance with applicable
pressure codes. The maximum standard relative operating pressure
is 2100 kPa for the refrigerant-side and 1000 kPa for the water-side.
These pressures can be different depending on the code applied.
The water connection of the heat exchanger is a Victaulic
connection.
24

Table of Contents

Related product manuals