3 - INSTALLATION SPECIFICS FOR 30RQSY UNITS
3.1 - General
Each fan is controlled by a variable-speed controller. Therefore 
each circuit operates independently and must have a separate 
duct  system  to  avoid  any  air  recycling  between  the  air  heat 
exchangers of the different refrigerant circuits. 
On  the  30RQSY  units  each  fan  includes  a  factory-mounted 
connection frame interface for the connection to the duct network 
of the specic refrigerant circuit to which the fan belongs.
For  the  precise  dimensions  of  this  connection  interface  please 
refer to the dimensional drawings for the units.
3.2 - Duct connection
30RQSY units can be installed inside a building and connected 
to a air distribution duct network:
- Air  heat  exchanger  side,  at  the  fresh  air  suction  side  for 
30RQSY 039 to 078 units
- Fan discharge side at the evacuation side of the treated air 
by the unit heat exchanger (30RQSY 039 to 160).
For  the  precise  dimensions  of  this  connection  interface  please 
refer to the dimensional drawings for the units.
Location of the air 
temperature sensor
3.2.1 - Standard unit suction connection
30RQSY 039 to 078 units are supplied with a sleeve that allows 
connection  of  an  air  heat  exchanger  suction  duct.  Provide  a 
removable window on the suction duct to allow the maintenance 
of the sensor (see gure above).
For units 30RQSY 050 to 078 the air heat exchanger is on two 
unit sides. It is therefore necessary to install two additional brackets 
to allow connection of the heat exchanger suction duct. 
These parts are inside the machine and xed to the riser (as shown 
on the diagram below) with plastic collars.
Specic connection precautions
for sizes 30RQSY 050 to 078
Air inlet
Air inlet
Air inlet
Air inlet
minimum
minimum
All dimensions are in mm.