EasyManua.ls Logo

Carrier AquaSnap Touch Pilot Junior Series - Supplementary Electric Resistance Heaters

Carrier AquaSnap Touch Pilot Junior Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
14.4 - Supplementary electric resistance
heaters
To permit staging of the capacity reduction of the heat pump at 
low ambient temperatures, as shown in the diagram below, it is 
possible to install supplementary electric heaters in the leaving 
water line. Their capacity can compensate for the capacity drop 
of the heat pump.
These heaters can be controlled via an electronic card mounted 
on a board (option). 
Four outputs are available to control the heater contactors (not 
supplied with the board), permitting gradual compensation of the 
heat pump capacity reduction.
These outputs are congurable to obtain a choice of two, three or 
four stages. The last stage will only be activated after a shut-down
of the heat pump following a fault con-dition (safety device).
In the diagram below “example of additional electric heaters” the 
capacity of the four heaters is the same as the capacity of the heat 
pump at 7°C outdoor air temperature.
This requires only a 400 V-3 ph-50 Hz power supply source, as 
well as a connection to the unit via a communication bus.
For the required conguration of the stages consult the 30RB/RQ 
Touch Pilot Junior Control IOM.
Typical accessory installation diagram
Legend
1  Electric heater power supply 400 V-3 ph-50 Hz
2  Accessory control board for four additional electric heaters
3  Internal communication bus
4  Heater stage control contactors
5  Power supply for additional heaters 
6  Supplementary electric resistance heaters
Example of additional electric heaters
Outdoor air temperature, °C
Pump capacity, %
Legend
1 Stage 1
2 Stage 2
3 Stage 3
4 Stage 4
A Heat pump capacity variation as a function of the air temperature
B Building thermal load
C Balance point between the capacity supplied by the heat pump and the thermal load of the building
Operating range, in which the heat pump capacity is lower than the building thermal load
Operating range, in which the heat pump capacity is higher than the building thermal load
14 - START-UP

Table of Contents

Related product manuals