EasyManua.ls Logo

Carrier AquaSnap Touch Pilot Junior Series - Units with Hydraulic Module and Variable-Speed Pump - Pressure Differential Control; Units with Hydraulic Module and Variable-Speed Pump - Temperature Difference Control

Carrier AquaSnap Touch Pilot Junior Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
13.2.2 - Procedure for cleaning the hydraulic circuit
Open all valves completely (item 19).
Start-up the system pump.
Let the pump run for 2 hours consecutively to clean up the 
hydraulic circuit of the system (presence of contaminating 
solids).
Perform another reading.
Compare this value to the initial value.
A reducing value of the ow indicates that the lters on the 
system need to be removed and cleaned. In this case, close 
the Shut-off valves on the water inlet and outlet (item 19) 
and remove the lters (items 20 and 1) after draining the 
hydraulic part of the unit (item 6). 
Remove the air from the circuit (items 5 and 14).
Repeat until the lter remains clean.
13.2.3 - Procedure for controlling water fow
Once  the  circuit  is  cleaned,  read  the  ow  value  on  the  user 
interface and compare it with design value for the system. If the 
value of the ow is greater than the specied value, this indicates 
that the overall pressure drop in the system is too low against the 
available static pressure generated by the pump.
In this case, close the control valve and read the ow value. Repeat 
as necessary until the pressure drop corresponding to the design 
ow rate is achieved.
NOTE: If the network has an excessive pressure drop in
relation to the available static pressure delivered by the unit
pump, the nominal water ow cannot be obtained (lower
resulting ow) and the difference in temperature between the
water inlet and outlet of the evaporator will be increased.
To reduce the hydraulic system pressure drop:
Reduce  the  pressure  drops  of  individual  components 
(bends, level changes, valves etc.) as much as possible
Use the correct pipe diameter
Do not extend the piping system.
13.3 - Units with hydraulic module and variable-
speed pump - pressure differential control
The system ow is not controlled to a xed value. The ow
rate will be adjusted, by varying the pump speed, to maintain a 
system  pressure  differential  value  defined  by  the  user.  The 
pressure sensor at the unit outlet (item 10 in the typical hydraulic 
circuit diagram) is used as the means of control.
The system calculates the measured pressure differential value, 
compares it with the user-selected set point value and modulates 
the pump speed as necessary. The result is:
an increased ow rate, if a lower value than the set point is 
measured,
an decreased ow rate, if a higher value than the set point 
is measured.
This ow rate variation is realised, observing the minimum and 
maximum admissible unit ow rates as well as the minimum and 
maximum pump supply frequency values.
The pressure differential value maintained can in certain cases 
be different from the set point value:
If the set point value is too high (achieved for a higher ow 
rate than the maximum value or a higher frequency than 
the maximum value), the system settles at the maximum 
ow rate or maximum frequency and this results in a lower 
pressure differential than the set point.
If the set point value is too low (achieved for a lower ow 
rate that the minimum value or a lower frequency than the 
minimum value), the system  settles at the minimum ow 
rate  or  minimum  frequency  and  this  results  in  a  higher 
pressure differential than the set point.
See with Carrier Service to implement the procedures described 
below.
13.3.1 - Procedure for cleaning the hydraulic circuit
Before  proceeding,  it  is  advisable  to  remove  any  possible
contamination from the hydraulic circuit.
Start-up  the  system  pump  by  using  the  forced  start
command.
Control the frequency to the maximum value to generate a 
higher ow.
If there is a ‘Maximum fow exceeded’’alarm, reduce the 
frequency until an acceptable value is reached.
Read the value of the ow on the user interface.
Let the pump run for 2 hours consecutively to clean up the 
hydraulic circuit of the system (presence of contaminating 
solids).
Perform another reading of the ow and compare this value 
with the initial value. A reducing value of the ow indicates 
that  the  lters  on  the  system  need  to  be  removed  and 
cleaned. In this case, close the shut-off valves on the water 
inlet and outlet (item 19) and remove the lters (items 12 
and 1) after draining the hydraulic part of the unit (item 6).
Remove the air from the circuit (items 5 and 14).
Repeat if required the lter remains clean.
13.3.2 - Procedure for controlling the pressure
differential
Setpoint
Once  the  circuit  is  cleaned,  place  the  hydraulic  circuit  in  the 
conguration for which the unit selection was performed generally 
(all valves open and all cooling coils active). Read the value of 
the !ow on the user interface and compare it with the theoretical 
value of the range:
If the value of the ow is greater than the specied value, 
reduce  the  pressure  differential  setpoint  on  the  user 
interface to reduce the value of the ow.
If  the  value  of  the  ow  is  lower  to  the  specied  value, 
increase  the  pressure  differential setpoint  on  the  user 
interface to increase the value of the ow.
Repeat until the design pressure drop / ow rate is achieved.
Stop  the  forced  operation  of  the  pump  and  proceed  to  the 
conguration of the unit for the required control mode.
Modify the control parameters:
- Set water ow control to ‘pressure differential’
- Set the value of the required differential pressure
By default, the unit is congured at the maximum speed (frequency: 
50 Hz).
NOTES:
If during controlling, the low or high frequency limits are
reached before reaching the specied ow, keep the pressure
differential value to its lower or higher limit to enter in the
control parameters.
If the user knows in advance the pressure differential value
at the unit outlet to be maintained, this value can be entered
directly as data to be declared. You should not, however,
avoid the sequence of cleaning the hydraulic circuit.
13.4 - Units with hydraulic module and variable-
speed pump - temperature difference control
The temperature probes at the heat exchanger inlet and outlet 
(items 8 and 9 in the typical hydraulic circuit diagram) are used 
as means of control.
The system reads the measured temperature values, calculates 
the corresponding temperature difference, compares it with the 
user-selected set point value and modulates the pump speed as 
necessary:
If a higher delta T value than the set point is measured, the 
ow rate is increased.
If a lower delta T value than the set point is measured, the 
ow rate is decreased.
13 - NOMINAL SYSTEM WATER FLOW CONTROL

Table of Contents

Related product manuals