EasyManua.ls Logo

Carrier AquaSnap Touch Pilot Junior Series - 5 Physical Data, 30 Rqs Units

Carrier AquaSnap Touch Pilot Junior Series
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
5 - PHYSICAL DATA, 30RQS UNITS
For units with fans with variable available pressure (30RQSY 039-160) please refer to chapter 7.
30RQS 039 045 050 060 070 078 080 090 100 120 140 160
Sound levels
Standard unit
Sound power level
(1)
dB(A) 80 81 81 86 87 87 84 84 84 84 90 90
Sound pressure level at 10 m
(2)
dB(A) 49 49 49 55 55 55 52 52 52 52 58 58
Standard unit + option 15LS
Sound power level 
(1)
dB(A) 79 80 80 80 80 80 83 83 83 83 83 83
Sound pressure level at 10 m 
(2)
dB(A) 48 48 48 48 48 48 51 51 51 51 51 51
Dimensions
Lenght mm 1090 1090 1090 1090 1090 1090 2273 2273 2273 2273 2273 2273
Depth mm 2109 2109 2109 2109 2109 2109 2136 2136 2136 2136 2136 2136
Height without buffer tank module mm 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330 1330
Height with buffer tank module mm 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930 1930
Operating weight
(3)
Standard unit without hydraulic module kg 497 504 533 546 547 554 739 886 894 953 1054 1072
Standard unit with hydraulic module
Single high-pressure pump kg 529 537 563 576 576 584 769 918 926 989 1093 1111
Dual high pressure pump kg 555 563 588 602 602 610 795 963 971 1037 1130 1148
Single high-pressure pump + Buffer tank module option
kg 925 933 959 972 972 980 1202 1351 1359 1422 1526 1544
Dual high pressure pump + Buffer tank module option
kg 951 959 984 998 998 1006 1228 1396 1404 1470 1563 1581
Compressors Hermetic scroll compressor 48.3 r/s
Circuit A 2 2 2 2 2 2 2 3 3 3 2 2
Circuit B - - - - - - - - - - 2 2
No. of capacity steps 2 2 2 2 2 2 2 3 3 3 4 4
Refrigerant charge
(3)
R-410A
Circuit A
kg 12.5 13.5 16.5 17.5 18.0 16.5 21.5 27.5 28.5 33.0 19.0 18.5
teqCO
2
26.1 28.2 34.5 36.5 37.6 34.5 44.9 57.4 59.5 68.9 39.7 38.6
Circuit B
kg - - - - - - - - - - 19.0 18.5
teqCO
2
- - - - - - - - - - 39.7 38.6
Oil charge POE SZ160 (EMKARATE RL-32-3MAF)
Circuit A l 5.8 7.2 7.2 7.2 7.0 7.0 7.0 7.2 7.0 7.0 7.0 7.0
Circuit B l - - - - - - - - - - 7.0 7.0
Capacity control type Touch pilot junior
Minimum capacity % 50 50 50 50 50 50 50 33 33 33 25 25
Air heat exchangers Grooved copper tubes, aluminium ns
Fans Axial Flying Bird VI fans with rotating shroud
Quantity 1 1 1 1 1 1 2 2 2 2 2 2
Maximum total air ow l/s 3692 3690 3910 5285 5284 5282 7770 7380 7376 7818 10568 10568
Maximum rotation speed r/s 12 12 12 16 16 16 12 12 12 12 16 16
Water heat exchanger Direct-expansion plate heat exchanger
Water volume
l 2.6 3.0 4.0 4.8 4.8 5.6 8.7 8.7 9.9 11.3 12.4 14.7
Without hydraulic module
Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
With hydraulic module (option)
Single or dual pump (as selected)
Pump, Victaulic screen lter, relief valve, expansion tank, water + air purge valves,
pressure sensors
Expansion tank volume l 12 12 12 12 12 12 35 35 35 35 35 35
Expansion tank pressure
(4)
bar 1 1 1 1 1 1 1 1.5 1.5 1.5 1.5 1.5
Max. water-side operating pressure  kPa 400 400 400 400 400 400 400 400 400 400 400 400
With Buffer tank module (option)
Single or dual pump (as selected)
Pump, Victaulic screen lter, relief valve, expansion tank,  purge valves (water + air),
pressure sensors
Water volume l 250 250 250 250 250 250 250 250 250 250 250 250
Expansion tank volume l 18 18 18 18 18 18 35 35 35 35 35 35
Expansion tank pressure
(4)
bar 1 1 1 1 1 1 1,5 1,5 1,5 1,5 1,5 1,5
Max. water-side operating pressure kPa 400 400 400 400 400 400 400 400 400 400 400 400
Water connections with and without hydraulic module Victaulic
Connections inch 2 2 2 2 2 2 2 2 2 2 2 2
Outside tube diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3
Chassis paint colour Colour code RAL 7035
(1)  In dB ref=10
-12
 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in 
accordance with ISO 9614-1 and certied by Eurovent.
(2)  In dB ref 20 μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, 
calculated from the sound power level Lw(A).
(3)  Weight shown is a guideline only. Please refer to the unit nameplate.
(4)  When delivered, the standard pre-ination of the tank is not necessarily the optimal value for the system. To permit changing the water volume, change the ination 
pressure to a pressure that is close to the static head of the system. Fill the system with water (purging the air) to a pressure value that is 10 to 20 kPa higher than the 
pressure in the tank. 

Table of Contents