Configuring the system
Carrier Connect™
Wi-Fi Thermostat Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation Guide 21 All rights reserved
Parameter Name/Description
Default and Range
STAGE DELAYThe minimum amount of time the current stage must be energized
before staging up to the next stage of capacity.
NOTE If the system demand is greater than 3°F, then this configuration is ignored for
the current heating or cooling cycle because the staging timers are canceled, to allow full
equipment capacity to meet the large demand.
D:
R:
10 MIN
2 MIN to 15 MIN
FORCED STAGE UPThe amount of time another stage of heat or cool is enabled if the
space temperature conditions are not improving. If the time in a current demanded stage
reaches the selected forced stage-up time, the thermostat stages up to the next
available stage of capacity, even if DIFFERENTIAL demand is not met.
D:
R:
30 MIN
OFF
10 MIN to 120 MIN in 10
minute increments
DIFFERENTIALThe required difference between the current space temperature and
the setpoint, before demand is initiated. This value is additive for each new stage of
equipment being demanded.
EXAMPLE A chosen DIFFERENTIAL value of 0.5°F requires 0.5°F difference between
setpoint and space temperature before first stage is turned on. Then, 1°F of difference
between setpoint and space temperature is necessary before the second stage is turned
on.
D:
R:
1.0°F
0.3°F to 2.0°F in 0.1°F
increments
AIR FILTER REMINDERThe number of hours before a SYSTEM EVENT reminds the
occupant to change the indoor air filter.
If set to OFF, a SYSTEM EVENT will not occur to remind the homeowner to change
the indoor air filter.
Decrements to the timer happen each hour of total equipment runtime.
Minutes are not stored in non-volatile memory, so a power reset clears out the
minutes within each hour of run time.
Once the number of hours is initially set or later changed, the filter tim
er must be
reset on the SETTINGS screen.
D:
R:
3000 HRS
OFF
500 HRS to 15000 HRS in
500 hour increments
OCCUPANCY OUTPUTWhen set to ON-(*) or ON-W2, selected relay output equals
current Occupancy state. Can be used for ECON Enable.
NOTE The OCCUPANCY OUTPUT option is not displayed or available if both (*) and W2
relays are being used; i.e. Humidification/ Heat Pump/ 3
-Stg Cool/ etc..
D:
R:
OFF
OFF
ON-(*)
ON-W2
OCCUPANCY INPUTThis setting changes the current heating and cooling setpoints to
the option selected for MAX HOLD TIME. This occurs when the short is detected on the
Remote Space Sensor for the duration of 2 to 5 seconds.
D:
R:
Occupied
Occupied
Unoccupied
LINE FREQUENCYUsed to increment operational timers within the thermostat to
ensure timing accuracy.
D:
R:
60HZ
50HZ
60HZ
DISCONNECT WIFI
Disconnects the thermostat from the Wi-Fi network.
CAUTION Disconnecting the Wi-Fi requires setting up the Connect Thermostat
using the Connect mobile application in order to re-establish Wi-Fi connectivity.
INSTALLATION TESTSee the Installation Test (page 37) section for detailed
instructions.