Humidification
There is occupied and unoccupied humidification on units that are equipped with humidifiers.
The following conditions must be true for humidification to operate:
HUMIDIFIER must be set to YES
Must not be configured for DEHUMIDIFY, HEAT PUMP, or COMPRESSOR EQUIPMENT STAGES =3
Must be in heating mode
Humidity must be 3% less than the humidify setpoint
Humidification ends when the humidity rises 3% above the humidify setpoint or the heating demand is satisfied.
Filter status
FILTER STATUS is based on a supply fan runtime, which you can configure from 500 to 3000 hours. A filter status
alert displays when the filter timer exceeds the configured number of hours. Press to see message.
Holidays
There is a maximum of 24 holiday periods. You can program each holiday period based on a start and stop month
date, or day of the month and week, with duration up to 365 days. The holiday schedule uses the first unoccupied
period setpoints for temperature control.