Humidification 
There is occupied and unoccupied humidification on units that are equipped with humidifiers.  
The following conditions must be true for humidification to operate: 
•  HUMIDIFIER must be set to YES 
•  Must not be configured for DEHUMIDIFY, HEAT PUMP, or COMPRESSOR EQUIPMENT STAGES =3 
•  Must be in heating mode 
•  Humidity must be 3% less than the humidify setpoint 
 
Humidification ends when the humidity rises 3% above the humidify setpoint or the heating demand is satisfied. 
 
 
 
 
 
Filter status 
FILTER STATUS is based on a supply fan runtime, which you can configure from 500 to 3000 hours. A filter status 
alert   displays when the filter timer exceeds the configured number of hours. Press to see message. 
 
 
 
 
Holidays 
There is a maximum of 24 holiday periods. You can program each holiday period based on a start and stop month 
date, or day of the month and week, with duration up to 365 days. The holiday schedule uses the first unoccupied 
period setpoints for temperature control.