17
ECONOMI$ER IV CONTROL MODES
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
(See Table 2.) The EconoMi$er IV assembly is supplied from the
factory with  a supply air temperature sensor,  a  low temperature
compressor lockout switch, and an outdoor air temperature sensor.
This  allows  for operation of  the EconoMi$er  IV assembly  with
outdoor  air  dry  bulb  changeover control. Additional  accessories
can be added to allow for different types of  changeover control
and operation of the EconoMi$er IV controller and unit.
OUTDOOR DRY BULB CHANGEOVER
The standard controller is shipped from the factory configured for
outdoor dry bulb changeover control. The outdoor air and supply
air temperature sensors are included as standard. For this control
mode,  the  outdoor  temperature  is  compared  to  a  selectable  set
point sensor. (See Fig. 39.) If the outdoor-air temperature is above
the set point, the EconoMi$er IV controller will adjust the outdoor
air damper to minimum position. If the outdoor-air temperature is
below the set point, the position of the outdoor-air dampers will be
controlled to provide free cooling using outdoor air. When in this
mode, the  LED  next to  the free cooling set point  potentiometer
will be on. The changeover temperature set point is selected by the
switches  on  the  sensor.  See  Fig.  39  for  the  corresponding
temperature changeover values.
OUTDOOR ENTHALPY CHANGEOVER
For  enthalpy  control,  accessory  enthalpy  sensor  (part  number
CRENTDIF004A00  for  Carrier  and  Bryant,  AXB078ENT  for
ICP)  is  required.  Replace  the  standard  outdoor  dry  bulb
temperature sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 38.) When the outdoor air enthalpy
rises  above  the  outdoor  enthalpy  changeover  set  point,  the
outdoor-air damper moves to its minimum position.
The outdoor  enthalpy changeover set point  is set  with the out-
door  enthalpy  set  point  potentiometer  on  the  EconoMi$er  IV
controller. The set points are A, B, C and D. (See Fig. 40.) The
factory-installed  620-ohm  jumper  must  be  in  place  across
terminals SR  and  SR+  on  the EconoMi$er IV controller. (See
Fig. 15.)
DIFFERENTIAL ENTHALPY CONTROL
For  differential  enthalpy  control,  the  EconoMi$er  IV  controller
(see  Fig.  41)  uses  two  enthalpy  sensors  (AXB078ENT  and
CRENTDIF004A00), one in the outside air and one in the return
airstream. The  EconoMi$er  IV  controller  compares  the  outdoor
air enthalpy to the return air enthalpy to determine EconoMi$er IV
controller use. The controller selects the lower enthalpy air (return
or outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air and is below the set point, the
EconoMi$er  IV  damper  opens  to  bring  in  outdoor  air  for  free
cooling.
Replace  the  standard  outside  air  dry  bulb  temperature  sensor
with  the  accessory  enthalpy  sensor  in  the  same  mounting
location. (See Fig. 38.) Mount the return air enthalpy sensor in
the  return  air  duct.  (See  Fig.  42.)  When  using  this  mode  of
changeover  control,  turn  the  enthalpy  set  point  potentiometer
fully clockwise to the D setting.
Fig. 39 — Selectable Temperature Options
ON
OFF
1  
 
2   3
1  
 
2   3
1  
 
2   3
1  
 
2   3
1  
 
2   3
1  
 
2   3
1  
 
2   3
1  
 
2   3
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
DIP SWITCH
POSITION
CHANGEOVER
TEMPERATURE
48°F
53°F
55°F
58°F
63°F
68°F
73°F
78°F