21
3. Use  the  Up/Down button to select  the  preset  number.  (See
Table 5.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of  the CO
2
 sensor can be changed anytime
after the sensor is energized. Follow the steps below to change the
non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds until
the sensor enter the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use  the  Up/Down  button  to toggle  to  the  NONSTD  menu
and press Enter.
4. Use the Up/Down button to toggle through each of the nine
variables,  starting  with Altitude,  until the  desired  setting  is
reached.
5. Press Mode to move through the variables.
6. Press  Enter  to  lock  in  the  selection,  then  press  Mode  to
continue to the next variable.
DEHUMIDIFICATION  OF  FRESH  AIR  WITH  DCV
CONTROL
Information  from ASHRAE  indicates  that  the  largest  humidity
load on any zone is the fresh air introduced. For some application,
an  energy  recovery  unit  can  be  added  to  reduce  the  moisture
content of the fresh air being brought into the building when the
enthalpy is  high. In  most cases, the normal heating and cooling
processes are more than adequate  to remove  the humidity loads
for most commercial applications. If normal rooftop heating and
cooling operation is not adequate for the outdoor humidity level,
and energy recovery unit and/or a dehumidification option should
be considered.
LEGEND
ppm — Parts Per Million
Table 5 — CO
2
 Sensor Standard Settings
SETTING  EQUIPMENT  OUTPUT
VENTILATION 
RATE 
(cfm/Person)
ANALOG 
OUTPUT
CO
2
 CONTROL 
RANGE 
(ppm)
OPTIONAL 
RELAY 
SETPOINT 
(ppm)
RELAY 
HYSTERESIS 
(ppm)
1
Interface w/Standard 
Building Control 
System
Proportional  Any 
0-10V 
4-20 mA 
0-2000  1000  50
2  Proportional  Any 
2-10V 
4-20 mA 
0-2000  1000  50
3  Exponential  Any 
0-10V 
4-20 mA 
0-2000  1100  50
4
Economizer
Proportional  15 
0-10V 
4-20 mA 
0-1100  1100  50
5  Proportional  20 
0-10V 
4-20 mA 
0-900  900  50
6  Exponential  15 
0-10V 
4-20 mA 
0-1100  1100  50
7  Exponential  20 
0-10V 
4-20 mA 
0- 900  900  50
8  Health and Safety  Proportional  —
0-10V 
4-20 mA 
0-9999  5000  500
9
Parking/Air Intakes/
Loading Docks
Proportional  — 
0-10V 
4-20 mA 
0-2000  700  50