4
ACCESSORIES LIST
The  EconoMi$er  IV  assembly  has  several  field-installed
accessories available to optimize performance. Refer  to Table  3
for authorized parts.
 
VERTICAL INSTALLATION
These  economizers  are  designed to  work  in  both a  vertical and
horizontal  applications.  These  instructions  are  for  a  vertical
installation.
1. Turn off unit power supply and install lockout tag.
2. Prepare the unit for economizer installation:
 a. For units with two position damper installed, remove the
outside  air  hood.  Unplug  the  damper  actuator  and
remove assembly from unit.
 b. For  units  with  manual  damper  installed,  remove  the
manual damper and hood.
3. Remove the upper panel and bottom panel (provided with the
HVAC  unit)  on  the  end  of  the  unit  to  expose  the  return
section.  (See  Fig.  2.)  Save  the  screws  for  use  later  when
replacing the panel. The panels can be discarded.
4. Remove  the  unit's  left  side  corner  post  and  left  side  panel
from the unit to allow for easy economizer installation. (See
Fig. 3.)
5. Install  economizer,  as  shown  in  Fig.  3,  into  the  return  air
section of the unit. Be careful not to pinch the wires during
installation.  The  bottom  of  the  economizer  will  rest  on the
base of the unit. (See Fig. 4.)
6. Reinstall  the  left  side corner  post  on  to  the  unit.  Note  the
corner  post  will  sit  behind  the  economizer  flange.  (See
Fig. 5.)  Screw  through  the  corner  post  and  through  the
economizer. (See Fig. 5 and 6.)
 
Fig. 2 — Upper and Bottom Panel on End of Unit
Fig. 3 — Unit Left Side Panel and Corner Post
Fig. 4 — Side View
7. Insert  provided  screw  through  the  bottom  left  rear  of  the
economizer and into the unit base. (See Fig. 4.) Reinstall the
unit's left side panel.
8. Before the economizer is secured in place on the right hand
side, remove and save the 12-pin jumper plug from the unit
wiring harness. (See Fig. 7.) Insert the economizer plug into
the unit wiring harness plug.
NOTE: The 12-pin jumper plug should be saved for future use in
the event that the EconoMi$er IV assembly is removed from the
unit. The jumper plug is not needed as long as the EconoMi$er IV
assembly is installed.
Table 3 — EconoMi$er IV Field-Installed Accessories 
DESCRIPTION  PART NUMBER
Power Exhaust 208-230 v 3 Ph  CRPWREXH068A00
Power Exhaust 460 v 3 Ph  CRPWREXH069A00
Power Exhaust 575 v 3 Ph  CRPWREXH070A00
Outdoor Air Enthalpy Sensor
HH57AC078
(Carrier and Bryant only)
AXB078ENT (ICP only)
Indoor Air Enthalpy Sensor  CRENTDIF004A00
Return Air CO
2
 Sensor (4 to 20 mA)  CRCBDIOX005A00
CO
2
 Room Sensor (4 to 20 mA) 33ZCSENC02
Aspirator Box for Duct Mount CO
2
 
(4 to 20 mA)
33ZCASPCO2
Space Temperature and CO
2
 Room 
Sensor with Override (4 to 20 mA)
33ZCT55CO2
Space Temperature and CO
2
 Room 
Sensor with Override and Set Point 
(4 to 20 mA)
33ZCT56CO2
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution can result in personal injury and
damage to the unit.
Cover the duct opening as a precaution so objects cannot fall
into the return duct opening. Be sure to remove the cover when
installation is complete.
Upper End Panel
Shipped On 
Base Unit
Bottom Panel
Shipped On 
Base Unit
Indoor Fan Panel
UNIT’S LEFT
SIDE PANEL
ECONOMI$ER IV
LEFT 
CORNER 
POST
Left
Corner
Post
Unit’s Left
Side Panel
Economizer IV
Economizer
Screw Economizer
To B as e