22
OPERATION
Sequence of Operation
When  free  cooling  is  not  available,  the  compressors  will  be
controlled by the zone thermostat. When free cooling is available,
the  outdoor-air  damper  is  modulated  by  the  EconoMi$er  IV
control to provide a 50°F to 55°F supply-air temperature into the
zone. As  the  supply-air  temperature  fluctuates  above  55°F  or
below  50°F,  the  dampers  will  be  modulated  (open  or  close)  to
bring the Supply-air temperature  back within  the set points. For
EconoMi$er IV operation, there must be a thermostat call for the
fan  (G).  This  will  move  the  damper  to  its  minimum  position
during the occupied mode.
Above  50°F  supply-air  temperature,  the  dampers  will  modulate
from  100% open to the  minimum open position. From  50°F to
45°F  supply-air  temperature,  the  dampers  will  maintain  at  the
minimum  open  position.  Below  45°F,  the  dampers  will  be
completely shut. As the supply-air temperature rises, the dampers
will  come  back  open  to  the  minimum  open  position  once  the
supply-air temperature rises to 48°F.
If optional power exhaust is installed, as the outdoor-air damper
opens and closes,  the  power exhaust fans will be energized and
de-energized.
If  field-installed  accessory  CO
2
  sensors  are  connected  to  the
EconoMi$er IV control, a demand controlled ventilation strategy
will begin to operate. As the CO
2 
level in the zone increases above
the CO
2
 set  point, the  minimum  position of the  damper will be
increased proportionally. As the CO
2
 level decreases  because of
the  increase  in  fresh  air,  the  outdoor-air  damper  will  be
proportionally  closed.  Damper  position  will  follow  the  higher
demand condition from DCV mode or free cooling mode.
Damper movement from full  closed to full open (or vice  versa)
will take between 1-1/2 and 2-1/2 minutes.
If  free  cooling  can be  used  as determined from  the  appropriate
changeover  command  (dry  bulb,  enthalpy  curve,  or  differential
enthalpy),  a  call  for  cooling  (Y1  closes  at  the  thermostat)  will
cause the control to modulate the dampers open to maintain the
supply air temperature set point at 50°F to 55°F.
As the supply air temperature drops below the set point range of
50°F to 55°F, the control will modulate the outdoor-air dampers
closed to maintain the proper supply-air temperature.
TROUBLESHOOTING
See Table 6 on page 24 for EconoMi$er IV system logic.
EconoMi$er IV System Preparation
This  procedure is used to prepare the EconoMi$er IV controller
for  troubleshooting.  No  troubleshooting  or  testing  is  done  by
performing the following procedure.
NOTE:  This  procedure  requires  a  9-v  battery,  1.2  kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied with
the EconoMi$er IV controller.
1. Disconnect power at TR and TR1. All LEDs should be off.
Exhaust fan contact should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect  wires at T  and  T1.  Place  5.6  kilo-ohm  resistor
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If  connected,  remove  sensor  from  terminals  SO  and  +.
Connect  1.2  kilo-ohm  checkout  resistor  across  terminals
SO and +.
8. Put 620-ohm resistor across terminals SR and +.
9. Set  minimum  position,  DCV  set  point,  and  exhaust
potentiometers fully CCW (counterclockwise).
10. Set  DCV  maximum  position  potentiometer  fully  CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy
To check differential enthalpy:
1. Make sure EconoMi$er IV system preparation procedure has
been performed.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free Cool
LED should be lit.
4. Remove 620-ohm resistor across SO and +. The  Free Cool
LED should turn off.
5. Return EconoMi$er  IV  settings  and  wiring  to  normal after
completing troubleshooting.
Single Enthalpy
To check single enthalpy:
1. Make sure the EconoMi$er IV system preparation procedure
has been performed.
2. Set the  enthalpy potentiometer to A (fully CCW). The Free
Cool LED should be lit.
3. Set  the  enthalpy  potentiometer  to  D  (fully  CW). The  Free
Cool LED should turn off.
4. Return EconoMi$er IV system settings and wiring to normal
after completing troubleshooting.
DCV (Demand Controlled Ventilation) and Power
Exhaust
1. Make  sure EconoMi$er  IV  preparation  procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for both
DCV and Exhaust should be off. The actuator should be fully
closed.
3. Connect  a  9-v  battery  to  AQ  (positive  node)  and  AQ1
(negative node). The LED for both DCV and Exhaust should
turn  on. The actuator should drive  to  between 90  and  95%
open.
4. Turn the Exhaust potentiometer CW until the Exhaust LED
turns off. The LED should turn off when the potentiometer is
approximately 90%. The actuator should remain in position.
5. Turn  the  DCV  set  point  potentiometer  CW  until  the DCV
LED  turns  off.  The  DCV  LED  should  turn  off  when  the
potentiometer is approximately 9-v. The actuator should drive
fully closed.
6. Turn  the  DCV and  Exhaust  potentiometers  CCW  until the
Exhaust LED turns on. The exhaust contact will close 30 to
120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er  IV  settings  and  wiring  to  normal after
completing troubleshooting.
IMPORTANT:  Be  sure  to  record  the  positions  of  all
potentiometers before starting troubleshooting.