8
Fig. 15 — Economizer Wiring Diagram
 
HORIZONTAL INSTALLATION
These  economizers  are  designed  to  work  in  both  vertical  and
horizontal  applications.  These  instructions  are  for  a  horizontal
application.
The  unit  has  a  horizontal  duct  opening  next  to  the  horizontal
supply  duct  opening.  However,  in  this  application,  with  an
economizer, the horizontal duct will  actually come into the unit
underneath the outdoor air hood. (See Fig. 16.)
1. Turn off unit power supply and install lockout tag.
2. Prepare the unit for economizer installation:
 a. For units with 2 position damper installed, remove the
outside  air  hood.  Unplug  the  damper  actuator  and
remove assembly from unit.
 b. For  units  with  manual  damper  installed,  remove  the
manual damper and hood.
3. Remove the upper panel and bottom panel (provided with the
HVAC  unit).  On  the  end  of  the  unit  to  expose  the  return
section.  (See Fig.  17.)  Save  the  screws  for  use  later  when
replacing the panel. The panels can be discarded.
4. Remove  the  unit's  left  side  corner  post  and  left  side  panel
from the unit to allow for easy economizer installation. (See
Fig. 18.)
NOTE: The unit's left side panel has a duct opening in it, but this
panel / duct opening will not be used in this application and can be
discarded.
5. Install  economizer, as  shown in  Fig.  19,  into  the return air
section of the unit. Be careful not to pinch the wires during
installation. Bottom of economizer will rest on the base of the
unit. (See Fig. 20.)
6. Reinstall  the  left  side  corner  post  on  to  the  unit.  Note  the
corner  post  will  sit  behind  the  economizer  flange.  (See
Fig. 21.)  Screw  through  the  corner  post  and  through  the
economizer. (See Fig. 21 and 22.)
7. Insert  provided  screw  through  the  bottom  left  rear  of  the
economizer and into the unit base. (See Fig. 20.) Install the
new (provided) left side panel - without the duct opening on
the unit.
8. Before the economizer is secured in place on the right hand
side, remove and save the 12-pin jumper plug from the unit
wiring harness. Insert the EconoMi$er IV plug into the unit
wiring harness plug. (See Fig. 23.)
NOTE: The 12-pin jumper plug should be saved for future use in
the event that the EconoMi$er IV assembly is removed from the
unit. The jumper plug is not needed as long as the EconoMi$er IV
assembly is installed.
POTENTIOMETER
POWER EXH
MINIMUM POS.
DCV MAX.
DCV SET
ENTHALPY
DEFAULTS SETTINGS:
MIDDLE
FULLY CLOSED
MIDDLE
MIDDLE
C SETTING
(ACCESSORY)
REMOTE MIN
POSITION POT
REMOTE POT (135 ohm)
(FIOP / ACCESSORY)
IAQ SENSOR
2
8
7
1
BRN
RED
RED
BLU
BLK
BLK
WHT
BLK
BLK
BLK
GRA
GRA
GRA
GRA
GRA
GRA
YEL
ORN
ORN
ORN
PNK
PNK
YEL
YEL
YEL
BLU
BLU
BLU
BLU
BLU
PNK
PNK
PNK
VIO
VIO
VIO
BLK
BRN
BRN
BRN
BRN
OAT TEMP /
ENTHALPY SENSOR
(ACCESSORY)
RAT/ENTHALPY SENSOR
+
5
AQ1
AQ
SO+
SO
SR+
SR
620Ω
N1
N
P1
T1
P
T
2V
2V
2V
10V
10V
10V
EXH
SET
EXH
MIN
POS
OPEN
DCV
MAX
DCV
SET
DCV
FREE
COOL
A
B
C
D
RED
RED
RED
RED
RED
RED
BRN
BRN
ECONOMISER
IV BOARD
TR
TR1
24
Vac
HOT
24Vac
COM
-
+
1
1
1
2
2
2
5
5
9
12
8
10
11
6
7
4
4
3
3
1
2
5
9
12
8
10
11
6
7
4
3
1
2
5
9
12
8
10
11
6
7
4
3
3
EF EF1
ECONOMIZER
MOTOR
LA
(NOT USED)
(NOT USED)
(NOT USED)
ESL
VIO
SAT
(FIOP / ACCY)
ECONOMIZER
PL6 - R
FOR STD
UNIT PL6
TAN
TO PWR EXHAUST
ACCESSORY
ECONOMIZER NOTES:
1.  620 OHM, 1 WATT 5% RESISTOR SHOULD BE REMOVED ONLY WHEN
USING DIFFERENTIAL ENTHALPY OR DRY BULB.
2.  IF A SEPARATE FIELD SUPPLIED 24V TRANSFORMER IS USED FOR THE
IAQ SENSOR POWER SUPPLY, IT CANNOT HAVE THE SECONDARY OF THE 
TRANSFORMER GROUNDED.
3.  FOR FIELD INSTALLED REMOTE MINIMUM POSITION POT.
REMOVE BLACK WIRE JUMPER BETWEEN P AND P1 AND SET
CONTROL MINIMUM POSITION POT TO THE MINIMUM POSITION.
ECONOMIZER (FIOP / ACCESSORY)
Economizer Unit Without Economizer