19
INDOOR AIR QUALITY (IAQ) SENSOR INPUT
The IAQ input can be used for demand control ventilation control
based on the level of CO
2
 measured in the space or return air duct.
Mount  the  accessory  IAQ  sensor  according  to  manufacturer
specifications. The  IAQ  sensor  should  be  wired  to  the AQ  and
AQ1 terminals of the controller. Adjust the DCV voltage output of
the indoor air quality sensor at the user-determined set point. (See
Fig. 43.) 
If a separate field-supplied transformer is used to power the IAQ
sensor,  the sensor  must not be  grounded or the  EconoMi$er  IV
control board will be damaged.
Fig. 42 — Return Air Temperature or Enthalpy Sensor 
Mounting Location
EXHAUST SET POINT ADJUSTMENT
The exhaust set point  will determine when the exhaust fan runs
based on damper position (if accessory power exhaust is installed).
The set point is modified with the Exhaust Fan Set Point (EXH
SET)  potentiometer.  (See  Fig.  44.) The  set  point  represents the
damper position above which the exhaust fans will be turned on.
When there  is  a call for  exhaust, the  EconoMi$er IV  controller
provides a 45 ±15 second delay before exhaust fan activation to
allow the dampers to open. This delay allows the damper to reach
the appropriate position to avoid unnecessary fan overload.
Fig. 43 — CO
2
 Sensor Maximum Range Setting
MINIMUM POSITION CONTROL
There  is  a  minimum  damper  position  potentiometer  on  the
EconoMi$er IV controller. (See Fig. 44.) The minimum damper
position maintains the minimum airflow into the building during
the occupied period.
When  using  demand  ventilation,  the  minimum  damper  position
represents  the  minimum  ventilation  position  for  VOC  (volatile
organic  compound)  ventilation  requirements.  The  maximum
demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum
position  potentiometer  should  be  used  to  set  the  occupied
ventilation position. When not using a CO
2
 sensor, the DCV MAX
potentiometer  must  be  fully  closed  (CCW)  for  the  Minimum
Position potentiometer to function correctly.
Adjust  the  minimum  position  potentiometer  to  allow  the
minimum  amount  of outdoor  air, as required  by local codes, to
enter the building. Make minimum  position adjustments with at
least  10°F  temperature  difference  between  the  outdoor  and
return-air temperatures.
To determine the minimum position setting perform the following
procedure:
1. Calculate  the  appropriate  mixed  air  temperature  using  the
following formula:
T
O
 = Outdoor-Air Temperature
OA = Percent of Outdoor Air
T
R
 = Return-Air Temperature
RA = Percent of Return Air
T
M
 = Mixed-Air Temperature
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure  that  the  factory-installed  jumper  is  in  place  across
terminals  P  and  P1.  If remote  damper  positioning  is being
used,  make  sure  that  the  terminals  are  wired  according  to
Fig. 15  and  that  the  minimum  position  potentiometer  is
turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully  adjust  the  minimum  position  potentiometer  until
the measured mixed-air temperature  matches the calculated
value.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when
requiring  additional  temporary  ventilation.  If  a  field-supplied
remote  potentiometer  is wired to  the  EconoMi$er IV  controller,
the  minimum  position  of  the  damper  can  be  controlled  from  a
remote location.
To  control  the  minimum  damper position,  remotely remove the
factory-installed  jumper  on  the  P  and  P1  terminals  on  the
EconoMi$er IV controller. Wire the field-supplied potentiometer
to the P and P1 terminals on the EconoMi$er IV controller. (See
Fig. 15.)
DAMPER MOVEMENT
Damper movement from full  open to full closed (or vice  versa)
takes 2-1/2 minutes.
THERMOSTATS
The EconoMi$er IV control works with conventional thermostats
that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage 1),
W2 (heat stage 2), and G (fan). The EconoMi$er IV control does
not support space temperature sensors. Connections are made at
the  thermostat  terminal  connection  board  located  in  the  main
control box.
Return AiR
Sensor
Return Duct
(Field-provided)
0
1000
2000
3000
4000
5000
6000
2345678
RANGE CONFIGURATION (ppm)
DAMPER VOLTAGE FOR MAX VENTILATION RATE
CO SENSOR MAX RANGE SETTING
2
800 ppm
900 ppm
1000 ppm
1100 ppm
T
O
 x OA + (T
R
 x RA ) = T
M
100 100