Table 6 — EconoMi$er IV Input/Output Logic
*  For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†  Power at B terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**  Modulation is based on the supply-air sensor signal.
††  Modulation is based on the DCV signal.
***  Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully
open (supply-air signal).
††† Modulation is  based on the  greater of DCV  and  supply-air  sensor signals,  between  closed and  either maximum position (DCV) or fully open
(supply-air signal).
INPUTS  OUTPUTS
Demand 
Controlled 
Ventilation (DCV)
Enthalpy*
Y1  Y2
Compressor  N Terminal†
Outdoor  Return
Stage 
1
Stage 
2
Occupied  Unoccupied
Damper
Below set 
(DCV LED Off)
High 
(Free Cooling LED Off) 
Low
On  On  On  On
Minimum position  ClosedOn  Off  On  Off 
Off  Off  Off  Off
Low 
(Free Cooling LED On) 
High
On  On  On  Off  Modulating**
(between min. position and 
full-open)
Modulating**
(between closed and full-
open)
On  Off  Off  Off 
Off  Off  Off  Off  Minimum position  Closed
Above set 
(DCV LED On)
High 
(Free Cooling LED Off) 
Low
On  On  On  On
Modulating††
(between min. position and 
DCV maximum)
Modulating††
(between closed and DCV 
maximum)
On  Off  On  Off
Off  Off  Off  Off
Low 
(Free Cooling LED On) 
High
On  On  On  Off
Modulating*** Modulating†††On  Off  Off O ff 
Off  Off  Off  Off