83
Cooling Percentage R
Input Register
(Float)
9 clg_pct AV 13 nvoClgPct
SNVT_count_inc(
9)
Network Status of Cool-
ing Demand in percent-
age (%)
Cooling Set point R/W
Holding Regis-
ter (Float)
57 sat_stpt_cl AV 66 Select
Network Parameter to
set the Cooling Set point
55 °F (Default)
CSAT_HI R Discrete Input 28 csat_hi BV 80 Select
Network Parameter to
set CSAT HI
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Current Alarm R
Input Register
(Float)
11 current_alarm AV 17
nvoCurAl
m
SNVT_count_inc(
9)
Alarm Status of unit:
0 = No Alarm
1-7 = UPM1 Fault Code
9-16 =UPM2 Fault Code
20 = Output Overridden
via Keypad
30 = Sensor Failure
40 = Leaving Water
Temp Alarm
50 = Zone Temp Alarm
60 = Discharge Air Tem-
perature
70 = Filter Alarm/Com-
pressors 1 & 2 Runtime
90 = High CO
2
Level
Alarm
100 = Supply Fan
Locked
110 = Static Press Low
CWV Command R Discrete Input 29
cwv_com-
mand
BV 109
nvoCwvCo
mmand
SNVT_switch(95)
Condenser Water Valve
Command Status
0 = Off
1 = On
CWV_FAIL R Discrete Input 30 cwv_fail BV 107 Select
Condenser Water Valve
Failure Alarm
CWV_HAND R Discrete Input 31 cwv_hand BV 108 Select
Condenser Hand Alarm
Condenser Valve Com-
mand Enabled without
unit commanded
DA_SENS_FAIL R Discrete Input 32 da_sen BV 31 Select
Network Alarm Indicat-
ing Discharge Air Sen-
sor Failure
0 = Normal
1 = Alarm
Damper Output
Cmd
R Discrete Input 33 damper_cmd BV 49
nvoDamp-
erCmd
SNVT_switch(95)
Damper Output Status
0 = Closed
1 = Open
DAT Sensor Selec-
tion
R/W
Holding Regis-
ter (Float)
15 dat_sel AV 81 Select
Discharge Air Tempera-
ture Sensor Setup
0 = Hardwired Sensor
(Default)
1= BAS Supplied DAT
value
DAT Sensor Source
Selection Status
R
Input Register
(Float)
13 dat_sel_sta AV 82 Select
Discharge Air Tempera-
ture Sensor Selection
Status
0 = Hardwired Sensor
DAT
1 = BAS Supplied DAT
DAT_HI R Discrete Input 34 dat_hi BV 29 Select
Discharge Air Tempera-
ture Sensor Alarm (Cool-
ing)
0 = Normal
1 = High DAT (Default:
>70 °F)
Demand Level R/W
Holding Regis-
ter (Float)
17 demand_level AV 64 Select
Demand Level Set point
Adjust in °F
DO_LOCK R Discrete Input 35 do_lock BV 37 Select
Network Parameter to
set DO LOCK
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
DPS Alarm R Discrete Input 36 DPS_alarm BV 77 Select
Network Parameter to
set DPS Alarm
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
DX_RNTM R Discrete Input 37 dx_rntm BV 79 Select
Network Parameter to
set DX RNTM
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Table 66 — Integration Points List (cont)
PROTOCOL MAP MODBUS BACNET LONWORKS OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME SNVT DESCRIPTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Omnizone 50BVC and is the answer not in the manual?

Carrier Omnizone 50BVC Specifications

General IconGeneral
BrandCarrier
ModelOmnizone 50BVC
CategoryAir Conditioner
LanguageEnglish

Related product manuals