9.2 - Alarms description
9.2.1 - Alarms
Name Code Description Reset Action taken Possible cause
1
COOL_EWT_F 15001 Water Exchanger Entering Fluid
Thermistor Failure
Automatic, if thermistor
reading returns to normal
Unit shuts down Defective thermistor
2 COOL_LWT_F 15002 Water Exchanger Leaving Fluid Thermistor
Failure
As above As above As above
3 DEFROST_T_A_F 15003 Circuit A Defrost Thermistor Failure As above Cooling mode: Unit
continues to operate
Heating mode: Circuit A
shuts down
As above
4 DEFROST_T_B_F 15004 Circuit B Defrost Thermistor Failure As above Cooling mode: Unit
continues to operate
Heating mode: Circuit B
shuts down
As above
5 OAT_F 15010 OAT Thermistor Failure As above Unit shuts down As above
6 CHWSTEMP_F 15011 MASTER/Slave Common Fluid Thermistor
Failure
As above Master/Slave operation is
disabled, each unit
returns to the stand-
alone mode
As above
7 SUCTION_T_A_F 15012 Circuit A Suction Gas Thermistor Failure As above Circuit A shuts down As above
8 SUCTION_T_B_F 15013 Circuit B Suction Gas Thermistor Failure As above Circuit B shuts down As above
9 SGTC1_F 15044 Coil Suction Gas Thermistor Sensor 1
Failure
As above Circuit A shuts down (in
heating mode);
None (in cooling mode)
As above
10 SGTC2_F 15045 Coil Suction Gas Thermistor Sensor 2
Failure
As above Circuit B shuts down (in
heating mode);
None (in cooling mode)
As above
11 DP_A_F 12001 Circuit A Discharge Pressure Transducer
Failure
Automatic, if sensor voltage
reading returns to normal
Circuit A shuts down Defective transducer
12 DP_B_F 12002 Circuit B Discharge Pressure Transducer
Failure
As above Circuit B shuts down As above
13 SP_A_F 12004 Circuit A Suction Pressure Transducer
Failure
As above Circuit A shuts down As above
14 SP_B_F 12005 Circuit B Suction Pressure Transducer
Failure
As above Circuit B shuts down As above
15 SIOB_CIR_A_
COM_F
4901 Loss of communication with SIOB Board
Number A
Automatic, if
communication is
re-established
Circuit A shuts down As above
16 SIOB_CIR_B_
COM_F
4902 Loss of communication with SIOB Board
Number B
As above Circuit B shuts down Bus installation fault,
communication error
17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above
18 COOLER_
FREEZE_F
10001 Water Exchanger Freeze Protection Automatic (the rst alarm in
the last 24 h) or Manual
Unit shuts down, the
water exchanger pump is
running
No water ow,
defective thermistor
19 LOW_SUCTION_A_F 10005 Circuit A Low Saturated Suction
Temperature
Automatic (the rst alarm in
the last 24 h) or Manual
Circuit A shuts down Pressure transducer
defective, EXV blocked or
lack of refrigerant
20 LOW_SUCTION_B_F 10006 Circuit B Low Saturated Suction
Temperature
As above Circuit B shuts down As above
21 HIGH_SH_A_F 10008 Circuit A High Superheat Manual Circuit A shuts down Pressure transducer
defective, temperature
sensor defective, EXV
blocked or lack of
refrigerant
22 HIGH_SH_B_F 10009 Circuit B High Superheat Manual Circuit B shuts down As above
23 LOW_SH_A_F 10011 Circuit A Low Superheat Manual Circuit A shuts down As above
24 LOW_SH_B_F 10012 Circuit B Low Superheat Manual Circuit B shuts down As above
25 COOLER_LOCK_F 10014 Interlock Failure Automatic (if the unit was
stopped) or Manual
Unit shuts down Customer interlock input
set on
26 CPA1_REVERSE_
ROT_F
10016 Compressor A1 Not Started Or Pressure
Increase not Established
Manual Compressor A1 shuts
down
Compressor breaker or
fuse fault, compressor
switch open
27 CPA2_REVERSE_
ROT_F
10017 Compressor A2 Not Started Or Pressure
Increase not Established
Manual Compressor A2 shuts
down
As above
28 CPA3_REVERSE_
ROT_F
10018 Compressor A3 Not Started Or Pressure
Increase not Established
Manual Compressor A3 shuts
down
As above
29 CPB1_REVERSE_
ROT_F
10020 Compressor B1 Not Started Or Pressure
Increase not Established
Manual Compressor B1 shuts
down
As above
30 CPB2_REVERSE_
ROT_F
10021 Compressor B2 Not Started Or Pressure
Increase not Established
Manual Compressor B2 shuts
down
As above
31 LOSS_COM_SM_F 10029 Loss of communication with System
Manager
Automatic, if
communication is
re-established
Unit returns to the
stand-alone mode
CCN bus installation
defective
32 LOSS_COM_MS_F 10030 Master/Slave communication Failure Automatic, if
communication is
re-established
Master/Slave operation is
disabled, the unit returns
to the stand-alone mode
CCN bus installation
defective