Setpoint Menu – SETPOINT
Point name Status Default Unit Displayed text* Description
1 csp1 -28.9 to 20.0
-20.0 to 68.0
7.0
44.6
°C
°F
Cooling Setpoint 1 Cooling setpoint 1
2 csp2 -28.9 to 20.0
-20.0 to 68.0
7.0
44.6
°C
°F
Cooling Setpoint 2 Cooling setpoint 2
3 hsp1 25.0 to 55.0
77.0 to 131.0
38.0
100.4
°C
°F
Heating Setpoint 1 Heating setpoint 1
4 hsp2 25.0 to 55.0
77.0 to 131.0
38.0
100.4
°C
°F
Heating Setpoint 2 Heating setpoint 2
5 ramp_sp 0.1 to 1.1
0.2 to 2.0
0.6
1.0
^C
^F
Ramp Loading Ramp loading
6 cauto_sp 3.9 to 50.0
39.0 to 122.0
23.9
75.0
°C
°F
Cool Changeover Setpt Cool changeover setpoint
7 hauto_sp 0 to 46.1
32.0 to 115.0
17.8
64.0
°C
°F
Heat Changeover Setpt Heat changeover setpoint
8 lim_sp1 0 to 100 100 % Switch Limit Setpoint 1 Switch limit setpoint 1
9 lim_sp2 0 to 100 100 % Switch Limit Setpoint 2 Switch limit setpoint 2
10 lim_sp3 0 to 100 100 % Switch Limit Setpoint 3 Switch limit setpoint 3
11 min_sct 26.7 to 60.0
80.0 to 140.0
40.0
104.0
°C
°F
Desuperheater Min Sct Desuperheater minimum saturated condensing
temperature
*Depends on the selected language (English by default).
(CONFIG)
Icon Displayed text* Description Name
General Cong General conguration GENCONF
Pump Conguration Pump conguration PUMPCONF
Heat/Cool Cong Heat/Cool conguration HCCONFIG
Reset Cong Reset conguration RESETCFG
User Conguration User conguration USERCONF
Schedule Schedule menu SCHEDULE
Holiday Holiday menu HOLIDAY
Broadcast Broadcast menu BROADCAST
Date/Time Date/time conguration DATETIME
Control Identication Control identication CTRL_ID
*Depends on the selected language (English by default).
CAUTION
Since specic units may not include additional features,
some tables may contain parameters that cannot be
congured for a given unit.