General Cong Menu – GENCONF
Point name Status Default Unit Displayed text* Description
1 lead_cir 0 to 2 0 - Cir Priority Sequence Circuit priority sequence
0=Auto 1=A Lead 2=B Lead 0 = Automatic changeover
1 = Circuit A lead
2 = Circuit B lead
2 seq_typ no/yes no - Staged Loading Sequence Staged loading sequence
3 ramp_sel no/yes no - Ramp Loading Select Ramp loading sequence
4 o_on_d 1 to 15 1 min Unit O to On Delay Unit OFF to ON delay
5 nh_limit 0 to 100 100 % Night Capacity Limit Night capacity limitation
6 nh_start 00:00 00:00 - Night Mode Start Hour Night mode start hour
7 nh_end 00:00 00:00 - Night Mode End Hour Night mode end hour
8 bas_menu 0 to 3 0 - Basic Menu Cong Basic menu conguration
0 = All Access 0 = All access
1 = no alarm menu 1 = Alarm menu
2 = no setpoint menu 2 = Setpoint menu unavailable
3 = 1 + 2 3 = Alarm and Setpoint menus are unavailable
*Depends on the selected language (English by default).
Pump Conguration Menu – PUMPCONF
Point name Status Default Unit Displayed text* Description
1 pump_seq 0 to 4 0 - Water Pumps Sequence Water pumps sequence
0 = No Pump 0 = No pump
1 = One Pump Only 1 = One pump only (units with one pump)
2 = Two Pumps Auto 2 = Two pumps automatic control
3 = Pump#1 Manual 3 = Pump 1 selected (units with two pumps)
4 = Pump#2 Manual 4 = Pump 2 selected (units with two pumps)
2 pump_del 24 to 3000 48 hour Pump Auto Rotation Delay Pump automatic rotation delay
3 pump_per no/yes no - Pump Sticking Protection Pump sticking protection
4 pump_sby no/yes no - Stop Pump During Standby Pump stopped when the unit is in standby
5 pump_loc no/yes yes - Flow Checked if Pump O Water ow is checked when the pump is o
*Depends on the selected language (English by default).
Heat/Cool Cong Menu – HCCONFIG
Point name Status Default Unit Displayed text* Description
1 auto_sel no/yes no - Auto Changeover Select Heating/Cooling automatic changeover
2 cr_sel 0 to 3 0 - Cooling Reset Select Cooling reset
3 hr_sel 0 to 3 0 - Heating Reset Select Heating reset
1=OAT, 0=None
2=Delta T
3= Analog (4-20mA)
0 = No reset
1 = Reset based on OAT
2 = Reset based on delta T
3 = Reset based on analog input (4-20 mA)
4 heat_th -20.0 to 0.0
-4.0 to 32.0
-15.0
5.0
°C
°F
Heating OAT Threshold Heating OAT threshold
5 boil_th -15.0 to 15.0
5.0 to 59.0
-9.9
14.2
°C
°F
Boiler OAT Threshold Boiler OAT threshold
6 ehs_th -5.0 to 21.1
23.0 to 70.0
5.0
41.0
°C
°F
Elec Stage OAT Threshold Electric heating stage OAT threshold
7 both_sel no/yes no - HSM Both Command Select HSM command
8 ehs_back no/yes no - 1 Elec Stage For Backup Electric heating stage for back-up
9 ehs_pull 0 to 60 0 min Electrical Pulldown Time Electrical pull-down time: It denes the time
between starting the unit and determining whether
the electric heating stage should be started
10 ehs_defr no/yes no - Quick EHS For Defrost Quick electric heating used for defrost
*Depends on the selected language (English by default).
Reset Cong Menu – RESETCFG
Point name Status Default Unit Displayed text* Description
1 COOLING RESET Cooling reset parameters
2 oatcr_no -10.0 to 51.7
14.0 to 125.0
-10.0
14.0
°C
°F
OAT No Reset Value OAT no reset value
3 oatcr_fu -10.0 to 51.7
14.0 to 125.0
-10.0
14.0
°C
°F
OAT Full Reset Value OAT full reset value
4 dt_cr_no 0 to 13.9
0 to 25.0
0
0
^C
^F
Delta T No Reset Value Delta T no reset value
5 dt_cr_fu 0 to 13.9
0 to 25.0
0
0
^C
^F
Delta T Full Reset Value Delta T full reset value